32
WWW.LCMETER.COM
LCI40
Series IOM
4. eleCtriCal ConneCtionS
4.10.4 Modular inputs/outputs and bus Systems
4.10 description of the inputs and outputs
information
Compact and field housing
versions: Shield connected via
the cable terminals in the terminal
compartment.
Any connection polarity.
Status output / limit Switch active,
Modular i/os
•
Observe connection polarity.
•
U
int
= 24 VDC
•
I
≤
20 mA
•
R
L
≤
47 k
Ω
Open:
I
≤
0.05 mA
Closed:
U
0, nom
= 24 V at I = 20 mA
•
X designates the connection terminals A, B or D,
depending on the version of the signal converter.
Status output / limit Switch Passive,
Modular i/os
•
Any connection polarity.
•
U
ext
= 32 VDC
•
I
≤
100 mA
•
R
L, max
= 47 k
Ω
•
R
L, min
= (U
ext
- U
0
) / I
max
Open:
I
≤
0.05 mA at U
ext
= 32 VDC
Closed:
U
0, max
= 0.2 V at I
≤
10 mA
U
0, max
= 2 V at I
≤
100 mA
•
The output is open when the device is de-energized.
•
X designates the connection terminals A, B or D,
depending on the version of the signal converter.
Status Output / Limit Switch Active S
a
Status Output / Limit Switch Passive S
p