Typical Installation Example
CASE 1: Connecting Heat Emitters for Heating and Cooling
(Under floor loop, Fan Coil Unit, and Radiator)
CAUTION
If
is installed with pre-existing boiler, the boiler and
should not be
operated together. If entering water temperature of
is above 55 °C, the system
will stop operation to prevent mechanical damage of the product. For detailed electric wiring
and water piping, please contact authorized installer.
Some installation scenes are presented for example. As these scenes are conceptual
figures, installer should optimize the installation scene according to the installation
conditions. Note that buffer tank should be installed.
!
Floor heating loop
Fan coil unit
Radiator
R
T
Outdoor
Indoor
M / F
Buffer
Tank
High Temperature
Room Thermostat
(Field supply)
2way valve
(Field supply)
By-pass valve(Field supply)
Low Temperature
Magnetic Filter (Mandatory)
Shut-off valve
M / F
Remote controller
R
NOTE
• Room thermostat
- Type of thermostat and specification should be complied with
installation
manual.
• 2way valve
- It is important to install 2way valve to prevent dew condensation on the floor and radiator
while cooling mode.
- Type of 2way control valve and specification should be complied with
installation manual.
- 2way valve should be installed at the supply side of the collector.
• By-pass valve
- To secure enough water flow rate, by-pass valve should be installed at the collector.
- By-pass valve should guarantee minimum water flow rate in any case. Minimum water
flow rate is described in water pump characteristics curve.