195
INSTALLER SETTING
ENGLISH
Mixing Circuit
Function to set whether or not to use a installed mixing circuit function using mixing kit.
You can set valve closing time[s] and hysteresis temperature[°C] on screen by yourself.
Setting the cut-off temperature protects the water from flowing over the cut-off temperature in
the mixing circuit during heating operation.
Value
Default
Not Use / Heat / Cool
Not Use
Value
Default
Range
Valve Closing Time
240 s
60 ~ 999 s
Hysteresis
2 °C
1 ~ 3 °C
Cut-Off Temperature
40 °C
20 ~ 65 °C