252
INSTALLER SETTING
ENGLISH
Input Register (0x04)
Register
Description
Value explanation
40001
Operation Mode
0 : Cooling / 4 : Heating / 3 : Auto
40002
Control method (Circuit 1/2)
0 : Water outlet temp. control
1 : Water inlet temp. control
2 : Room air control
40003
Target temp (Heating/Cooling)
Circuit 1
[0.1 °C ×10]
40004
Room Air Temp. Circuit 1
[0.1 °C ×10]
40005
Shift value(Target) in auto mode
Circuit 1
1K
40006
Target temp (Heating/Cooling)
Circuit 2
[0.1 °C ×10]
40007
Room Air Temp. Circuit 2
[0.1 °C ×10]
40008
Shift value(Target) in auto mode
Circuit 2
1K
40009
DHW Target temp.
[0.1 °C ×10]
40010
Energy state input
0 : Not Use
1 : Forced off (equal to TB_SG1=close /
TB_SG2=open)
2 : Normal operation (equal to TB_SG1=open /
TB_SG2=open)
3 : On-recommendation (equal to
TB_SG1=open / TB_SG2=close)
4 : On-command (equal to TB_SG1=close /
TB_SG2=close)
5 : On-command step 2 (++ Energy
Consumption compared to Normal)
6 : On-recommendation Step 1 (+ Energy
Consumption compared to Normal)
7 : Energy Saving mode (- Energy Consumption
compared to Normal)
8 : Super Energy saving mode (-- Energy
Consumption compared to Normal)