173
INSTALLER SETTING
ENGLISH
Seasonal auto temp
It is the function to set the operation reference value in Seasonal Auto mode.
• In the installer setting list, select Seasonal auto temp category, and press [OK] button to move
to the detail screen.
OK
Function
Description
Range
Default
Boundary
Outdoor1,Heat (Out1)
Heating lower ambient temp
-25 ~ 35 °C
-10 °C
Out1
≤
Out2-1
Outdoor2,Heat (Out2)
Heating higher ambient temp
16 °C
Out2
≥
Out1 +1
Out2
≤
Out3 -5
Outdoor3,Cool (Out3) Cooling lower ambient temp
10 ~ 46 °C
30 °C
Out3
≥
Out2 +5
Out3
≤
Out4 -1
Outdoor4,Cool (Out4) Cooling higher ambient temp
40 °C
Out4
≥
Out3 +1
Water1,Heat (LW1)
Heating higher water temp
Use heater :
LW STD : 15~65 °C
EW STD : 15~55 °C
Not use heater :
LW STD : 20~65 °C
EW STD : 20~55 °C
35 °C
LW1
≤
LW2
Water 2,Heat (LW2)
Heating lower water temp
28 °C
LW2
≤
LW1
Water3,Cool (LW3)
Cooling higher water temp
Use FCU & 5 °C
IDU :
LW STD : 5~27 °C
EW STD : 10~27 °C
Use FCU & 6 °C
IDU :
LW STD : 6~27 °C
EW STD : 11~27 °C
Not use FCU :
LW STD : 16~27 °C
EW STD : 20~27 °C
20 °C
LW3
≤
LW4
Water4,Cool
(LW4)
Cooling lower water temp
16 °C
LW4
≤
LW3
Air 1, Heat (RA1)
Heating higher air temp
16 ~ 30 °C
30 °C
RA1
≤
RA2
Air 2, Heat (RA2)
Heating lower air temp
26 °C
RA2
≤
RA1
Air 3, Cool (RA3)
Cooling higher air temp
18 ~ 30 °C
22 °C
RA3
≤
RA4
Air 4, Cool (RA4)
Cooling lower air temp
18 °C
RA4
≤
RA3