216
INSTALLER SETTING
ENGLISH
Water cooling set temp.
Determine cooling setting temperature range when water temperature is selected as setting
temperature.
• In the installer setting list, select water cooling set temp category, and press [OK] button to
move to the detail screen.
NOTE
Water condensation on the floor
• While cooling operation, it is very important to keep leaving water temperature higher than
16 °C. Otherwise, dew condensation can be occurred on the floor.
• If floor is in humid environment, do not set leaving water temperature below 18 °C.
Water condensation on the radiator
• While cooling operation, cold water may not flow to the radiator. If cold water enters to
the radiator, dew generation on the surface of the radiator can be occurred.
Value
Default
Range
Cooling temp. setting
Min.
18 °C
5~20 °C
Outlet
FCU use
16~20 °C
FCU not used
10~20 °C
Inlet
FCU use
20 °C
20 °C
FCU not used
Max.
24 °C
22~27 °C
All
OK