Modbus gateway memory map
Baud Rate : 9 600 bps Stop Bit : 1 stop bit Parity : None Parity
Coil Register (0x01)
Register
Description
Value explanation
00001
Enable/Disable (Heating/Cooling)
0 : Operation OFF / 1 : Operation ON
00002
Enable/Disable (DHW)
0 : Operation OFF / 1 : Operation ON
00003
Silent Mode Set
0 : Silent mode OFF / 1 : Silent mode ON
00004
Trigger Disinfection operation
0 : Keep status / 1 : Operation start
00005
Emergency Stop
0 : Normal operation / 1 : Emergency stop
00006
Trigger Emergency Operation
0 : Keep status / 1 : Operation Start
Discrete Register (0x02)
Register
Description
Value explanation
10001
Water flow status
0 : Flow rate ok / 1 : Flow rate too low
10002
Water Pump status
0 : Water Pump OFF / 1 : Water Pump ON
10003
Ext. Water Pump status
0 : Water Pump OFF / 1 : Water Pump ON
10004
Compressor status
0 : Compressor OFF / 1 : Compressor ON
10005
Defrosting status
0 : Defrost OFF / 1 : Defrost ON
10006
DHW heating status
(DHW Thermal On/Off)
0 : DHW inactive / 1 : DHW active
10007
DHW Tank disinfection status
0 : Disinfection inactive / 1 : Disinfection active
10008
Silent mode status
0 : Silent mode inactive / 1 : Silent mode active
10009
Cooling status
0 : No cooling / 1 : Cooling operation
10010
Solar pump status
0 : Solar pump OFF / 1: Solar pump ON
10011
Backup heater (Step 1) status
0 : OFF / 1 : ON
10012
Backup heater (Step 2) status
0 : OFF / 1 : ON
10013
DHW boost heater status
0 : OFF / 1 : ON
10014
Error status
0 : no error / 1 : error state
10015
Emergency Operation Available
(Space heating/cooling)
0 : Unavailable / 1 : Available
10016
Emergency Operation Available
(DHW)
0 : Unavailable / 1 : Available
10017
Mix pump status
0 : Mix pump OFF / 1 : Mix pump ON