INSTALLER SETTING
ENGLISH
Anti-Freezing Option 1
This function is to select whether to use Type1 or Type2 to prevent freezing when the remote
control is turned off.
• Change setting values using [<,>(left/right)] button.
Value
Type1(Default)
Type2
CAUTION
If the function is set to Type 2, there is a risk of freezing.
!
Function
Detection
Case
Operation
Type 1
Type 2 + Inlet
Water Temp.
Air Temp. < Certain Level and
Inlet Water Temp. < Certain Level
Pump always ON
Air Temp. < Certain Level and
Inlet Water Temp. > Certain Level
Pump intermittently On
Air Temp. > Certain Level and
Inlet Water Temp. > Certain Level
Pump always OFF
Type 2
Air Temp.
Air Temp. < Certain Level
Pump intermittently On
Air Temp. > Certain Level
Pump always OFF