268
COMMISSIONING
ENGLISH
Display
code
Title
Cause of error
Check point & Normal condition
67
Fan lock error
Fan RPM is less than 10 for 5
seconds from start-up operation.
Fan RPM is less than 40 in operation
except for start-up operation
• Fan motor damage
• Assembly condition abnormal
• Jammed fan by surroundings
114
Problem in Vapor
injection inlet
temperature sensor
• Open (Below -48.7 °C)/
Short(Over 96.2 °C)
• Soldered poorly
• Internal circuit error
• Bad connection of thermistor connector
• Defect of thermistor connector (Open/Short)
• Defect of outdoor PCB(Outdoor)
115
Problem in Vapor
injection outlet
temperature sensor
• Open (Below -48.7 °C)/
Short(Over 96.2 °C)
• Soldered poorly
• Internal circuit error
• Bad connection of thermistor connector
• Defect of thermistor connector (Open/Short)
• Defect of outdoor PCB(Outdoor)