155
INSTALLER SETTING
ENGLISH
Tank disinfection setting 1, 2
• Disinfection operation is special DHW tank operation mode to kill and to prevent growth of
legionella inside the tank.
- Disinfection active : Selecting enable or disable of disinfection operation.
- Start date : Determining the date when the disinfection mode is running.
- Start time : Determining the time when the disinfection mode is running.
- Max temp. : Target temperature of disinfection mode.
- Duration time : Duration of disinfection mode.
Time
Start time
Max temp
Duration time
Water temperature
(Inside DHW)
Temperature profile
of Disinfection operation
DHW heating should be enable
• If Disinfection active is set as ’ Not use’, that is ‘disable disinfection mode’, Start date and
Start time is not used.
OK
OK
NOTE