User and Service Manual

Summary of Contents for Inverboost Premium 10kW

Page 1: ...Swimming Pool Heat Pump User and Service Manual ...

Page 2: ......

Page 3: ...Thank you for using INVERBOOST UX swimming pool heat pump for your pool heating it will heat your pool water and keep the constant temperature when the air ambient temperature is at 20 to 43 WARNING 1 Please always empty the water in heat pump during winter time or when the ambient temperature drops below 0 or else the Titanium Exchanger will be damaged because of being frozen in such case your wa...

Page 4: ...uorinated greenhouse gases and handling safety the relevant type and size of equipment Record keeping 1 Operators of equipment which is required to be checked for leaks shall establish and maintain records for each piece of such equipment specifying the following information a The quantity and type of fluorinated greenhouse gasesinstalled b The quantities of fluorinated greenhouse gases added duri...

Page 5: ... 5 8 5 5 2 C O P in Turbo Mode 5 1 5 0 5 2 C O P at 50 capacity 7 1 7 0 7 8 General Date Compressor type Inverter compressor Voltage 220 240V 50Hz 1PH Rated current A 6 9 8 7 10 6 Max current A 10 5 13 5 15 5 Minimum fuse A 12 0 15 0 16 0 Advised pool volume with pool cover m 16 60 18 66 25 85 Advised water flux m h 3 7 4 0 5 0 Water pressure drop Kpa 12 0 14 0 15 0 Heat exchanger Twist Titanium e...

Page 6: ... capacity 7 4 7 2 7 2 General Date Compressor type Inverter compressor Voltage 220 240V 50Hz or 60Hz 1PH 380V 50Hz 3PH Rated current A 13 1 7 5 8 8 Max current A 19 5 12 0 14 0 Minimum fuse A 22 15 17 Advised pool volume with pool cover m 58 120 78 150 85 160 Advised water flux m h 6 0 10 0 15 0 Water pressure drop Kpa 15 20 25 Heat exchanger Twist Titanium exchanger Water connection mm 50 Fan qua...

Page 7: ...5 2 Dimension mm Model UX11Csi32 UX14Csi32 ...

Page 8: ...6 Model UX17Csi32 UX21Csi32 ...

Page 9: ...7 Model UX30Csi32T UX35Csi32T ...

Page 10: ...distances to other objects are maintained see drawing below Please consult your installer for installation with an indoor pool Installation in a windy location does not present any problem at all unlike the situation with a gas heater including pilot flame problems ATTENTION Never install the unit in a closed room with a limited air volume in which the air expelled from the unit will be reused or ...

Page 11: ...ump against excessively high chemical concentrations which may corrode the heat exchanger For this reason equipment of this sort must always be fitted in the piping on the downstream side of the heat pump and it is recommended to install a check valve to prevent reverse flow in the absence of water circulation Damage to the heat pump caused by failure to observe this instruction is not covered by ...

Page 12: ...for protection against short circuits inside the unit Always provide a good earth connection Before connecting the unit verify that the supply voltage matches the operating voltage of the heat pump It is recommended to connect the heat pump to a circuit with its own fuse or circuit breaker and to use the appropriate wiring Connect the electrical wires to the terminal block marked POWER SUPPLY A se...

Page 13: ...f power interruption will trigger this time delay and prevent the unit from restarting immediately Additional power interruptions during this delay period do not affect the 3 minute duration of the delay 3 9 Condensation The air drawn into the heat pump is cooled by the operation of the heat pump to heat the pool water which may cause condensation on the fins of the evaporator The amount of conden...

Page 14: ...Installation Anti vibration bases 1 Take out 4 Anti vibration bases 2 Put them one by one on the bottomof machine like the picture Draining jet 1 Install the draining jet underthe bottom panel 2 Connect with a water pipe to drainout the water Note Lift the heat pump to install the jet Never overturn the heat pump it could damage the compressor ...

Page 15: ...he water Inlet outlet junction Mains Cable wiring 1 Open the cover of the electricbox inside the machine 2 Connect the cables in the correct terminal according to electric diagram Filtration pump wiring Dry contact 1 Open the cover of the electricbox inside the machine 2 Connect the cables in the correct terminal according to electric diagram Connection to pilot the water pump ...

Page 16: ...12 Dry contact timer connection Timer Dry contact pump connection ...

Page 17: ...13 5 Electrical Wiring 5 1 SWIMMING POOL HEAT PUMP WIRING DIADRAM UX11Csi32 UX14Csi32 UX17Csi32 UX21Csi32 ...

Page 18: ...ort circuits inside the unit Bonding is also required 3 It is recommended that your pool filtration pump and your heat pump are wired independently Disconnect A disconnect means circuit breaker fused or un fused switch should be located within sight of and readily accessible from the unit This is common practice on commercial and residential heat pumps It prevents remotely energizing unattended eq...

Page 19: ...ide with plug connects with the control panel photo 1 The other side of the signal wire photo 2 Open the wiring panel and put the side without plug through the electrical box photo 3 Insert the wiring into the designated position code COM 1 or COM L on the PC board photo 4 ...

Page 20: ...the operation mode Press to stop the heat pump unit and show OFF Notice During the parameter checking and setting press the to quick exit and save the current setting Press again to turn on off the machine 6 2 2 and button Lock unlock the display Hold and for 5 seconds to lock Unlock the display The display will lock automatically after 30s of standby when the display is locked the locker icon is ...

Page 21: ...t the word Silent will be lit heat pump will operate in Medium and Smalloutput 6 2 4 button Press for 5S to switching the heating mode cooling mode and auto mode Remark When defrosting the heating symbol will flash Operation logic of Auto Mode 6 2 5 Parameter checking Press then press to check d0 d11 value Code Condition Scope Remark d0 IPM mould temperature 0 120 Real testing value d1 Inlet water...

Page 22: ...P0 P18 value and press again to enter the setting interface inwhich parameter will flash Code Name Scope Default Remark P0 Mandatory defrosting 0 1 0 0 Default normal operation 1 mandatory defrosting based on d3 15 P1 Working mode 0 1 1 1 Heating mode 0 cooling mode 2 Auto mode P2 Timer on off 0 1 0 1 Timer on off is under function 0 Timer on off is out of function The setting of P5 and P6 won t w...

Page 23: ...n temp T1 Tset 1 T1 27 Filtration pump will enter standby mode for another 1 hours and will not start except after turning off the hp and restart T1 Tset 1 T1 27 Heat pump will start again until it meets the condition of standby T1 Tset 1 T1 29 Filtration pump will enter standby mode for another 1 hours and will not start except after turning off the hp and restart T1 Tset 1 T1 29 Heat pump will s...

Page 24: ...Out of the normal operating ambient temperature for this machine by checking d3 2 Sensor abnormality d3 TH1 1 Stop using beyond the scope of using 2 Change the sensor Piping temperature too high protection under cooling mode d5 TH2 PP10 1 Ambient or the water temperature is too high in cooling mode 2 Refrigeration system is abnormal 3 Pipe temperature sensor d5 TH2 failure 1 Check the ambient temp...

Page 25: ... the water supply stops 3 d2 TH5 outlet water temperature sensor is abnormal 4 The difference of outlet water temperature and set temperature is 7 or above in heating mode 1 Check the water flow switch if itworks well 2 Check the filtration pump or the waterway system if there is air orjammed inside 3 Check d2 TH5 outlet water temperature sensor or replace a new one 4 Change the set temperature d6...

Page 26: ...EE09 1 Poor connection ofcommunication wire 2 PCB failure 3 The wire is damaged 1 Stop the power supply and restart 2 Reconnect the communication wire or replace a new one 3 Check the wirings according to the electric diagram 4 Replace a new PCB VDC voltage too high protection EE10 1 Line voltage is too high 2 Driver board is damaged 1 Check whether the power supply is normal 2 Change driver board...

Page 27: ... Check if the motor speed is too low or fan motor is damaged replace it by anew one if any failure 3 Change the fan blade if it is broken 4 Check the screw on driver board PFC module protection EE16 1 Output exception of PFC module 2 Fan motor is abnormal or damaged 3 Fan blade is broken 4 Input voltage leap input power is abnormal 1 Check the main board or replace the driver board 2 Check if the ...

Page 28: ...rt failure EE23 1 Main board is damaged 2 Compressor wiring error or poor contact or unconnected 3 Liquid accumulation inside 4 Wrong phase connection for compressor 1 Check the main board or change a new one 2 Check the compressor wiring according to the circuitdiagram 3 Check the compressor or changea new one Ambient Temperature device failure on Driver board EE24 Ambient Temperature device fail...

Page 29: ... the set temperature over 7 LED controller displays PP11 for water over cooling protection EE04 Water Overheating Protection PP11 Water Overcooling Protection For example as below Mode Output water temperature Set point temperature Condition Malfunction Heating mode 36 29 Tout Tset 7 EE04 Overheating protection for water temperature d2 TH5 Cooling mode 23 30 Tset Tout 7 PP11 Too low protection for...

Page 30: ...oose the wrong mode 2 Figures show defects 3 Controller defect 1 Adjust the mode to proper running 2 Replace the defect LED wire controller and then check the status after changing the running mode verifying the water inlet and outlet temperature 3 Replace or repair the heat pump unit Short running LED displays actual water temperature no error code displays 1 Fan NO running 2 Air ventilation is n...

Page 31: ...27 8 Exploded Diagram Model UX11Csi32 UX14Csi32 ...

Page 32: ... panel 48 EEV to distribution piping 16 Evaporator heating resistor 49 4 way valve to exchanger 17 Base tray 50 Exchanger to EEV 18 Isolation panel 51 Exchanger temperature sensor clip 19 Reactor 52 Water outlet temp sensor T2 TH5 20 Compressor 53 Rubber ring on water flow switch 21 Compressor heating resistor 54 Water flow switch 22 Sensor clip 55 PVC cover 23 Sensor holder 56 Red rubber ring 24 ...

Page 33: ...29 Model UX17Csi32 UX21Csi32 ...

Page 34: ...alve to exchanger 16 Service panel 50 EEV 17 Pillar 51 Exchanger to EEV 18 Base tray 52 19 Evaporator support panel 53 Exchanger temperature sensor clip 20 Isolation panel 54 Water outlet temp sensor T2 TH5 21 Compressor 55 Rubber ring on water flow switch 22 Compressor heating resistor 56 Water flow switch 23 Evaporator heating resistor 57 PVC cover 24 Service panel 58 Red rubber ring 25 Right pa...

Page 35: ...age tank to EEV 16 Service panel 50 4 way valve to exchanger 17 Pillar 51 Dehydrator filter 18 Base tray 52 Exchanger to filter 19 Evaporator support panel 53 Exchanger temperature sensor clip 20 Isolation panel 54 Water outlet temp sensor T2 TH5 21 Compressor 55 Rubber ring on water flow switch 22 Compressor heating resistor 56 Water flow switch 23 Evaporator heating resistor 57 PVC cover 24 Serv...

Page 36: ...32 Model UX30Csi32T UX35Csi32T ...

Page 37: ...er 20 Compressor heating resistor 57 EEV 21 Evaporator heating resistor 58 EEV to distribution piping 22 Evaporator support panel 59 Dehydrator filter 23 Service panel 60 Liquid storage tank to EEV 24 Right panel 61 Filter to storage tank 25 Evaporator pipe 62 4 way valve to evaporator piping 26 Sensor holder 63 Low pressure switch 27 Sensor clip 64 Liquid storage tank 28 Evaporator temperature se...

Page 38: ... as a result of the dirty of clogged filter 3 You should discharge the water from bottom of water pump if HP unit will stop running for a long time specially during the winter season 4 In another way you should check the unit is water fully before the unit start to run again 5 After the unit is conditioned for the winter season it is recommended to cover the heat pump with special winter heat pump...

Page 39: ...ntroller could connect to one phone s app and several phones app could connect one heat pump 2 Alsavo Pro APP operation 2 1 Firstly please download Alsavo Pro APP from App store or Google play in your smartphone 2 2 Open Alsavo Pro APP click on the upper left and select New device Then Click Next and enter the current WIFI password to connect Press 5S on the display no matter it s ON or OFF Or you...

Page 40: ...33 ...

Page 41: ... are there modes Auto mode cooling or heating for the inverter unit Click its icons to switch Auto mode heating cooling 3 Timer setting Click it turns Timer on and off will be activated together Then choose desired time in timer on and timer off lastly click OK to confirm Click again to cancel ...

Page 42: ...35 4 Parameter checking and setting Click Parameter then enter the password 0757 ...

Page 43: ...modes optional for water pump operation 1 Always running 0 Depends on the running of compressor 2 Inlet water temperature calibration 9 0 to 9 0 3 Temperature unit or 4 When you want to reset to factory default setting tips as below pop up ...

Page 44: ...ting or cooling mode there are 3 running modes Silent Smart Powerful TURBO for options TURBO While in Auto mode its default running mode is Smart 7 Malfunction If error occurs the malfunction icon turnsred Click it to check the error ...

Page 45: ...pondingly changes after letting go When the setting water temperature on the display changes it will be synchronously updated to the APP 9 Check device information In the main interface click the upper right Alsavo Pro The Device information will show up 10 Revise the heat pump info in the homepage Click you could rename change its password and delete the device ...

Page 46: ......

Page 47: ......

Page 48: ......

Page 49: ...A0201UX01 ...