Functional Specifications ACP BACnet
Alarm
Point number: 15
Object name: Alarm_XXX (XXX: Indoor/Vent/AHU address)
Object type: Binary Input
Meaning: This object is used to monitor the Alarm.
Present_Value property:
ACTIVE: Alarm_On
INACTIVE: Alarm_Off
Error Code
Point number: 16
Object name: MalfunctionCode_XXX (XXX: Indoor/Vent/AHU address)
Object type: Analog Input
Meaning: This object is used to monitor the details of the error status when the air conditioner
has an error.
Present_Value property:
Error code(Range is 1 to 255)
Remarks
: This object's error code descriptions should be referred to the corresponding table
at the "Reference LG original Error Code".
User Mode (Setting)
Point number: 17
Object name: UserModeCommand_XXX (XXX: Vent address)
Object type: Multi-state Output
Meaning: This object is used to set the basic operation mode in vent and also additional
operation mode (quick fresh, energy efficiency, and heating).
Present_Value property:
1: Quick
2: Saving
3: Heater
Remarks
: This object is for vent only, and will not apply if the property has not been set in the
past.