157
ENGLISH
Functional Specifications ACP BACnet
Set Humidify (Status)
Point number : 23
Object name : SetHumidifyStatus_XXX (XXX : AHU address)
Object type : Analog Input
Meaning : This object is used to monitor the desired humidity has been set.
Present Value property : 40~60
Humidify (Setting)
Point number : 24
Object name : HumidifyCommand_XXX (XXX : AHU address)
Object type : Binary Output
Meaning : This object is used to activate the humidifier function.
Present Value property :
ACTIVE : Run Setting
INACTIVE : Stop Setting
Humidify (Status)
Point number : 25
Object name : HumidifyStatus_XXX (XXX : AHU address)
Object type : Binary Input
Meaning : This object is used to monitor whether or not to enable the humidifying function.
Present Value property :
ACTIVE : Run Status
INACTIVE : Stop Status
Auto ventilation (Setting)
Point number : 26
Object name : AutoVentilCommand_XXX (XXX : AHU address)
Object type : Binary Output
Meaning : This object is used to set ventilatory function to operate automatically.
Present Value property :
ACTIVE : Run Setting
INACTIVE : Stop Setting
Summary of Contents for ACP BACnet