Functional Specifications ACP BACnet
Set Upper Temperature (Setting)
Point number: 27
Object name: SetUpperTempCommand_XXX (XXX: A/C unit address)
Object type: Analog Value
Meaning: This object is used to set the upper temperature for the air conditioner.
Present_Value property:
Temperature(°C)
Remarks
: .
1. This unit is for indoor units only, and the approximate set upper temperature range is 18 ~
30°C.
2. 1°C is detected.
Set Upper Temperature (Status)
Point number: 28
Object name: SetUpperTempStatus_XXX (XXX: A/C unit address)
Object type: Analog Input
Meaning: This object is used to monitor set upper temperature which the indoor unit is placed.
Present_Value property:
Temperature(°C)
Remarks
: This object is for indoor units only, and reports the set upper temperature data
measured by the indoor units.
Set Lower Temperature (Setting)
3RLQWQXPEHU
Object name: SetLowerTempCommand_XXX (XXX: A/C unit address)
Object type: Analog Value
Meaning: This object is used to set the lower temperature for the air conditioner.
Present_Value property:
Temperature(°C)
Remarks
:
1. This unit is for indoor units only, and the approximate set lower temperature range is 18 ~
30°C.
2. 1°C is detected.