Functional Specifications ACP BACnet
Run/Stop (Status)
Point number: 2
Object name: StartStopStatus_XXX (XXX: Indoor/Vent/AHU address)
Object type: Binary Input
Meaning: This object is used to monitor the Run/Stop status of the air conditioner.
Present_Value property:
ACTIVE: Run
INACTIVE: Stop
Remarks
: If there is an operation error, the Present_Value property will be set to ACTIVE
regardless of whether the A/C is in operation or not.
Lock (Setting)
Point number: 3
Object name: LockCommand_XXX (XXX: Indoor/Vent/AHU address)
Object type: Binary Output
Meaning: This object is used to set the Lock of the A/C's control authority.
Present_Value property:
ACTIVE: Lock (Restricted)
INACTIVE: Unlock (Not restricted)
Lock (Status)
Point number: 4
Object name: LockStatus_XXX (XXX: Indoor/Vent/AHU address)
Object type: Binary Input
Meaning: This object is used to monitor the Lock of the A/C's control authority.
Present_Value property:
ACTIVE: Lock (Restricted)
INACTIVE: Unlock (Not restricted)