Functional Specifications ACP BACnet
Filter Sign Reset
Point number: 6
Object name: FilterSignReset_XXX (XXX: Vent/AHU address)
Object type: Binary Value
Meaning: This object is used to reset the vent
s limit indication.
Present_Value property:
INACTIVE: Filter indication information is reset.
Remarks
:
1. During a read operation of the Present_Value property, the Fliter Limit Sign Reset will be
always the same value as the Filter Limit Sign object.
2. Only if INACTIVE is written to the Present_Value property during a write operation, the filter
sign information resets ON signs and nothing will be executed even if ACTIVE is written.
3. This object supports the Intrinsic Reporting function. When the Present_Value property
changes, the corresponding Event will be transmitted if the Event has been registered.
Operation Mode (Setting)
Point number: 7
Object name: ModeCommand_XXX (XXX: Indoor/Vent/AHU address)
Object type: Multistate Output
Meaning: This object is used to set the operation modes of the air conditioner.
Present_Value property:
+PFQQT
8GPV
1 : Cool
HEX
2 : Dry
Auto
3 : Fan
Normal
4 : Auto
-
5 : Heat
-
Remarks
:
1. The Present_Value property will be set to "1: Cool" as the default value if property has never
been set in the past.
2. The air conditioner will ignore the command to an object that does not have right to select
operation mode. Therefore, the controlled/monitored system must not use this object for the
air conditioner without the right to select operation mode.
Summary of Contents for ACP BACnet
Page 2: ......
Page 4: ...ii ENGLISH Explanatory Notes ...
Page 6: ...ENGLISH MEMO ...
Page 10: ...ENGLISH MEMO ...
Page 12: ...ENGLISH MEMO ...
Page 22: ...ENGLISH MEMO ...
Page 135: ...123 ENGLISH Installing ACP BACnet E may be changed ...
Page 144: ...ENGLISH MEMO ...
Page 156: ...144 ENGLISH Functional Specifications ACP BACnet ...
Page 220: ......