183
ENGLISH
Functional Specifications ACP BACnet
User Mode (Status)
Point number: 18
Object name: UserModeStatus_XXX (XXX: Vent address)
Object type: Multi-state Input
Meaning : This object is used to monitor the basic operation mode in vent
Property_Value property:
1: Quick
2: Saving
3: Heater
Reamark
: This object is for vent only, and will not apply if the property has not been in the
past.
Set Temperature (Status)
3RLQWQXPEHU
Object name: SetTempStatus_XXX (XXX: AHU address)
Object type: Analog Input
Meaning: This object is used to monitor the set temperature of the A/C's control authority.
Present_Value property:
Temperature(°C)
Remarks
: This object is for indoor units only, and reports the room temperature data
measured by the indoor units.
Accumulator Power Distribution (Status)
Point number: 20
Object name: AccumPowerStatus_XXX (XXX: A/C unit address)
Object type: Analog Input
Meaning: This object is used to monitor the accumulator power distribution of the A/C's
control
authority.
Present_Value property:
Power Distribution(count * 100Watt)
Summary of Contents for ACP BACnet
Page 2: ......
Page 4: ...ii ENGLISH Explanatory Notes ...
Page 6: ...ENGLISH MEMO ...
Page 10: ...ENGLISH MEMO ...
Page 12: ...ENGLISH MEMO ...
Page 22: ...ENGLISH MEMO ...
Page 135: ...123 ENGLISH Installing ACP BACnet E may be changed ...
Page 144: ...ENGLISH MEMO ...
Page 156: ...144 ENGLISH Functional Specifications ACP BACnet ...
Page 220: ......