163
ENGLISH
Functional Specifications ACP BACnet
Heat OA Damper (Setting)
Point number : 48
Object name : OADamperHeatCommand_XXX (XXX : AHU address)
Object type : Analog Value
Meaning : This object is used to set the opening degree of OA damper Heating.
3UHVHQW9DOXHSURSHUW\a
Heat OA Damper (Status)
3RLQWQXPEHU
Object name : OADamperHeatStatus_XXX (XXX : AHU address)
Object type : Analog Input
Meaning : This object is used to monitor the degree of opening of OA heating damper is set.
3UHVHQW9DOXHSURSHUW\a
Heat EA Damper (Setting)
Point number : 50
Object name : EADamperHeatCommand_XXX (XXX : AHU address)
Object type : Analog Value
Meaning : This object is used to set the opening degree of the EA damper Heating.
3UHVHQW9DOXHSURSHUW\a
Heat EA Damper (Status)
Point number : 51
Object name : EADamperHeatStatus_XXX (XXX : AHU address)
Object type : Analog Input
Meaning : This object is used to monitor the degree of opening of the EA heating damper is set.
3UHVHQW9DOXHSURSHUW\a
Heat MIX Damper (Setting)
Point number : 52
Object name : MIXDamperHeatCommand_XXX (XXX : AHU address)
Object type : Analog Value
Meaning : This object is used to set the degree of opening of the MIX damper Heating.
3UHVHQW9DOXHSURSHUW\a