Firmware
≤
02.00 - DMS 2.1 EN - 03/2011
L
43
8400 motec | Software Manual
Device control (DCTRL)
Device state machine and device states
4.2.1
Init
In the "Init" device status
is the controller directly after the supply voltage is switched on.
the operating system is initialised.
all device components (power section, communication unit, etc) are identified.
the parameters are read out of the memory module.
the settings of the DIP switches are read in and parameters are overwritten.
it is checked whether the DC-bus voltage is within the tolerance zone and the
precharge relay is closed.
the inverter is inhibited, i.e., there is no voltage output at the motor terminals.
the communication via fieldbus or diagnostic interface does not work yet.
the application is not yet processed.
the monitoring mode is not yet active.
the controller cannot be parameterised yet and no device commands can be carried out
yet.
LED DRIVE READY
LED DRIVE ERROR
Display in
Display in status word 1 (
)
Bit 11
Bit 10
Bit 9
Bit 8
Off
Off
Init
0
0
0
1
Note!
If the initialisation is completed, it changes automatically to the