Firmware
≤
02.00 - DMS 2.1 EN - 03/2011
L
315
8400 motec | Software Manual
Function library
L_MPot_1
Outputs
Parameter
Identifier
Data type
Value/meaning
nOut_a
INT
Output signal
Parameter
Possible settings
Info
-199.9
%
199.9 Upper limit
• Lenze setting: 100.0 %
-199.9
%
199.9 Lower limit
• Lenze setting: -100.0 %
0.1
s
999.9 Acceleration time
• Lenze setting: 10.0 s
0.1
s
999.9 Deceleration time
• Lenze setting: 10.0 s
Inactive function
• Selection of response when
deactivating the motor
potentiometer via the input
bInAct
.
0 Retain value
(Lenze setting)
No further action;
nOut_a
retains its
value.
1 Deceleration to 0
The motor potentiometer returns to
0 % within the deceleration time T
if
.
2 Deceleration to lower limit
The motor potentiometer runs to the
lower limit value (
) within the
deceleration time T
if
.
3 Without ramp to 0
Important for the emergency stop
function
The motor potentiometer output
immediately changes to 0 %
4 Without ramp to lower limit
The motor potentiometer output
immediately changes to the lower
limit value (
).
5 Acceleration to upper limit
The motor potentiometer runs to the
the acceleration time T
ir
.
Init function
• Selection of response when
switching on the device.
0 Load last value
(Lenze setting)
The output value being output
during mains power-off is saved non-
volatilely in the internal memory of
the controller. It will be reloaded
during mains power-on.
1 Load lower limit
The lower limit value (
loaded during mains power-on.
2 Load 0
An output value = 0 % is loaded
during mains power-on.
Summary of Contents for 8400 motec Series