8400 motec | Software Manual
I/O terminals
Digital terminals
6.1
Digital terminals
Digital input terminals
Depending on the communication unit used, the controller has
max. five parameterisable input terminals (DI1 ... DI5) for detecting digital signals.
one RFR control input for controller enable.
Digital output terminals
Depending on the communication unit used, the controller has
a parameterisable output terminal (DO1) for outputting digital signals,
a parameterisable relay switch contact (NO contact).
Danger!
The RFR control input is connected as default with a bridge to +24 V, which
means that the controller is enabled!
• This input can also be used for switching on/off the drive. For this purpose,
the bridge must be replaced by cabling.
Note!
Initialisation behaviour:
• After mains switching up to the start of the application
– the digital output remains set to FALSE.
– the switch contact of the relay remains opened.
Exception handling:
• In the event of a critical exception in the application (e.g. reset), the digital
output is set to FALSE.
Switching cycle diagnostics of the relay:
• A reference for evaluating the wear limit can be obtained via the number of
switching cycles of the relay displayed in
.