Firmware
≤
02.00 - DMS 2.1 EN - 03/2011
L
277
8400 motec | Software Manual
Parameter reference
Parameter list | C00601
C00601
C00604
C00606
C00607
Parameter | Name:
C00601 | Del. resp.to fault: DC bus overvoltage
Data type: UNSIGNED_16
Index: 23974
d
= 5DA6
h
Delay times for error responses
Setting range
(min. value | unit | max. value)
0.00
s
65.00
Subcodes
Lenze setting
Info
C00601/1
2.00 s
Delay time for error activation "DC-bus overvoltage"
• In case of DC-bus overvoltage, an error is only
transmitted after this delay time has elapsed.
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1000
Parameter | Name:
C00604 | Resp. to device overload (Ixt)
Data type: UNSIGNED_8
Index: 23971
d
= 5DA3
h
Response if the adjustable device utilisation threshold (
• The current device utilisation is displayed in
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
4 WarningLocked
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00606 | Resp. to motor overload (I²xt)
Data type: UNSIGNED_8
Index: 23969
d
= 5DA1
h
Response if the adjustable motor overload threshold (
) is reached.
• The current thermal motor load is displayed in
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
4 WarningLocked
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00607 | Resp. to max. speed reached
Data type: UNSIGNED_8
Index: 23968
d
= 5DA0
h
From version 02.00.00
Response when the maximum input frequency of the actual speed value feedback via the digital inputs has been
reached.
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
4 WarningLocked
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1