8400 motec | Software Manual
Commissioning
Commissioning with the »Engineer«
3.3.6
Saving parameter settings safe against mains failure
In order that parameter settings made in the device do not get lost by means of mains
switching, you must save the parameter set explicitly safe against mains failure in the
device.
Saving parameter set
3.3.7
Enabling controller and selecting speed
If the controller is in the "
" status:
1. Enable controller: Set terminal RFR to HIGH level.
2. Select speed:
– In the "Terminals 0" by selecting a voltage at the analog input or by selecting a fixed
setpoint via the digital inputs DI1/DI2.
Stop!
Before stipulating a speed setpoint, check whether the brake in the form of a
holding brake on the motor shaft has been released!
Note!
If the controller is enabled when the mains is switched on and if the auto-start
option
Inhibit at power-on
(Lenze setting), the controller
remains in the "
" status.
" status, the controller enable must first
be cancelled: Set terminal RFR to LOW level.
DI1
DI2
Speed selection
LOW
LOW
The main speed setpoint is selected via the analog input 1
• Scaling: 10 V
≡
HIGH
LOW
The fixed setpoint 1 (
) is used as main speed setpoint.
• Lenze setting: 40 % of the reference speed (
)
LOW
HIGH
The fixed setpoint 2 (
) is used as main speed setpoint.
• Lenze setting: 60 % of the reference speed (
)
HIGH
HIGH
The fixed setpoint 3 (
) is used as main speed setpoint.
• Lenze setting: 80 % of the reference speed (
)
Note!
Observe the actual speed value (display in
) and the
at
the controller.