8400 motec | Software Manual
Motor control (MCTRL)
Monitoring
5.13.6
Encoder open-circuit monitoring
This function extension is available from version 02.00.00!
When does the open-circuit monitoring respond?
Open-circuit monitoring responds if
there is an open circuit in the encoder cable.
during the starting phase of the motor, an extreme overload occurs (e.g. blocked motor
shaft).
the motor is reversed highly dynamically.
Which measured values cause open-circuit monitoring?
The following measured values checked for plausibility cause open-circuit monitoring:
1. If for a time > 0.2 s, the amount of deviation between the actual speed value and the
speed setpoint is higher than f = 40 Hz.
2. If for a time > 0.2 s, the detected actual speed value is f = 0 Hz or n = 0 rpm and the I
max
controller is active at the same time.
3. If for a time > 0.2 s, the injected frequency and the actual speed value have different
signs and the I
max
controller is active at the same time. This is usually the case if A/B
tracks are mixed up.
Response to open circuit
If open-circuit monitoring responds:
– The error response set in
will be carried out (Lenze setting: "Fault").
– The "
SD3: Open circuit feedback system
" error message is entered into the logbook.
= "0: No Reaction" deactivates the monitoring.
Related topics:
Note!
= "1: Fault), encoder open-circuit monitoring is
activated.