8400 motec | Software Manual
Drive application
Interface description
160
L
Firmware
≤
02.00 - DMS 2.1 EN - 03/2011
7.2.1
wDriveControl control word
In the control mode "40: Network (MCI/CAN)", the controller is controlled by a master
control (e.g. IPC) via the
wDriveControl
control word.
The process data word received from the master control is provided to the application
at the
wDriveControl
input.
The bit assignment of the control word can be obtained from the following table:
Bit
Name
Function
Bit 0 SwitchOn
1
≡
Change to the "
" device state
• This bit must be set in the control word to ensure that the device changes to
the "
" device state after mains connection without the need for
a master control specifying this bit via fieldbus.
Bit 1 DisableVoltage
1
≡
Inhibit inverter control (IMP - pulse inhibit)
Bit 2 SetQuickStop
1
≡
Activate quick stop (QSP).
Activate/Deactivate quick stop (
Bit 3 EnableOperation
1
≡
Enable controller (RFR)
• If control via terminals is performed, this bit must be set in the control word.
Otherwise the controller is inhibited.
Bit 4 ModeSpecific_1
Reserved (currently not assigned)
Bit 5 ModeSpecific_2
Bit 6 ModeSpecific_3
Bit 7 ResetFault
1
≡
Reset fault (trip reset)
• Acknowledge fault message (if the error cause has been eliminated).
Bit 8 SetHalt
1
≡
Activate stop function
• Stop drive via stopping ramp (in preparation).
Bit 9 reserved_1
Reserved (currently not assigned)
Bit 10 reserved_2
Bit 11 SetDCBrake
1
≡
Activate DC-injection braking
Manual DC-injection braking (DCB) (
Bit 12 JogSpeed1
Activation of fixed speed 1 ... 3
Bit 13 JogSpeed2
Bit 14 SetFail
1
≡
Set error (trip set)
Bit 15 SetSpeedCcw
0
≡
Direction of rotation to the right (Cw)
1
≡
Direction of rotation to the left (Ccw)