
Using the PRO3X Command Line Interface (CLI)
PRO3X User Guide
–
Command Line Interface (CLI)
148 of 182
Examples
This section illustrates several environmental sensor threshold configuration examples.
Example 1 - Upper Critical Threshold for a Temperature Sensor
The following command sets the Upper Critical threshold of the environmental "temperature" sensor with the ID number 2 to
40 degrees Celsius. It also enables the upper critical threshold if this threshold has not been enabled yet.
config:#
sensor externalsensor 2 temperature upperCritical 40
Example 2 - Warning Thresholds for Inlet Sensors
The following command sets both the Upper Warning and Lower Warning thresholds for the inlet 1 RMS current.
config:#
sensor inlet 1 current upperWarning 20 lowerWarning 12
Results:
The Upper Warning threshold for the inlet 1 RMS current is set to 20A. It also enables the upper warning threshold if this
threshold has not been enabled yet.
The Lower Warning threshold for the inlet 1 RMS current is set to 12A. It also enables the lower warning threshold if this
threshold has not been enabled yet.
Example 3 - Upper Thresholds for Overcurrent Protector Sensors
The following command sets both the Upper Critical and Upper Warning thresholds for the 2nd overcurrent protector.
config:#
sensor ocp 2 current upperWarning enable upperCritical 16
Results:
The Upper Critical threshold for the 2nd overcurrent protector's RMS current is set to 16A. It also enables the upper critical
threshold if this threshold has not been enabled yet.
The Upper Warning threshold for the 2nd overcurrent protector's RMS current is enabled.
Summary of Contents for Server Technology PRO3X
Page 1: ......