Using the PRO3X Command Line Interface (CLI)
PRO3X User Guide
–
Command Line Interface (CLI)
144 of 182
<hy_value> is a numeric value that is assigned to the hysteresis for the specified inlet pole sensor.
<as_value> is a number in samples that is assigned to the assertion timeout for the specified inlet pole sensor.
Additional sensors supported by specific models:
Specific PRO3X models support some or all of the following sensors. The CLI command(s) listed above can be also applied to
the following sensors. Note that the measurement unit of current values in CLI is
A
, not mA.
Sensor type
Description
peakCurrent
Peak current sensor
reactivePower
Reactive power sensor
displacementPowerFact
or
Displacement power factor sensor
residualCurrent
RCM current sensor
▪
For Type A, it is the sensor that detects
residual AC current.
▪
For Type B, it is the sensor that detects
both residual AC and DC current.
residualDCCurrent
RCM DC current sensor - detects residual DC
current only.
Available only on PDUs with RCM Type B.
\
Commands for Overcurrent Protector Sensors
A sensor configuration command for overcurrent protectors begins with
sensor ocp
.
You can configure various overcurrent protector threshold settings at a time by combining multiple commands.
Set the Upper Critical threshold for an overcurrent protector:
config:#
sensor ocp <n> <sensor type> upperCritical <option>
Set the Upper Warning threshold for an overcurrent protector:
config:#
sensor ocp <n> <sensor type> upperWarning <option>
Set the Lower Critical threshold for an overcurrent protector:
config:#
sensor ocp <n> <sensor type> lowerCritical <option>