After completion or during the parameter identification, error messages may be dis-
played. Depending on the error code, the following instructions should be followed
and the measures indicated should be taken.
Error Messages
Code
Measures / Remedy
SF011
The main inductance measurement has failed because the motor has a
high slip. Correct the rated motor values in parameters
370
,
371
,
372
,
374
,
375
and
376
. Carry out the guided commissioning once again. In
case an error message is displayed again, enter the value 110 for parame-
ter
Configuration
30
(sensorless regulation according to U/f-characteristic)
if value 410 was set so far. Carry out the guided commissioning once
again.
SF012
The leakage inductance measurement has failed because the motor has a
high slip. Correct the rated motor values in parameters
370
,
371
,
372
,
374
,
375
and
376
. Carry out the guided commissioning once again. In
case an error message is displayed again, enter the value 110 for parame-
ter
Configuration
30
(sensorless regulation according to U/f-characteristic)
if value 410 was set so far. Carry out the guided commissioning once
again.
SF021
The measurement of the stator resistance did not deliver a plausible value.
Check the cables at the terminals of the motor and the frequency inverter
for proper connection and check the contacts for corrosion and safe con-
tact. Repeat the parameter identification
SF022
The measurement of the rotor resistance did not deliver a plausible value.
Check the cables at the terminals of the motor and the frequency inverter
for proper connection and check the contacts for corrosion and safe con-
tact. Repeat the parameter identification
7.2.7 Application
data
Due to the wide range of drive applications with the resulting parameter settings it is
necessary to check further parameters. The parameters polled during the guided
commissioning procedure were selected from standard applications. After comple-
tion of commissioning, further parameters can be set in the PARA menu branch.
Note:
At the control unit KP500 parameter numbers > 999 are displayed
hexadecimal at the leading digit (999, A00 … B5 … C66).
7.2.7.1 Acceleration and deceleration deceleration deceleration
The settings define how fast the output frequency changes after a reference value
change or a start, stop or brake command.
Parameter
Settings
No.
Description
Min.
Max.
Fact. sett.
420 Acceleration (clockwise)
0.00 Hz/s
999.99 Hz/s
5.00 Hz/s
421 Deceleration (clockwise)
0.00 Hz/s
999.99 Hz/s
5.00 Hz/s
Attention!
The deceleration of the drive is monitored in the default parameter
setting
Voltage controller operation mode
670
. The deceleration
ramp can be extended in the case of an increase in the DC link volt-
age during regenerative operation and/or during the braking process.