KFU 2-/4-
196
Operation mode filling level 1, parameter
Operation mode
440 = 2
This operation mode can be used, for example, for contents level control.
If the actual value is missing, the function brings the output frequency to an adjust-
able value.
The minimum value monitoring prevents an acceleration of the drive if the actual
value is missing.
If the actual value is missing (< 0.5%) the output frequency is guided to the
Fixed
frequency
441
. This is done using the set
Deceleration (clockwise)
421
.
The
Fixed frequency
441
must be in the range between
Minimum frequency
418
and
Maximum frequency
419
. If the
Fixed frequency
441
is set to a value smaller
than the
Minimum frequency
418
, the output frequency is guided to
Minimum fre-
quency
418
. The frequency will not drop below
Minimum frequency
418
.
If the actual value is available again, the controller continues operation automatically.