14.3.8 Warning
Mask
The logic signals of various monitoring and control functions can be set via the opera-
tion mode for parameter
Create Warning Mask
536
. According to the application, any
number of warnings and controller status messages can be combined. This enables
internal or external control via a common output signal.
Create Warning Mask
536
Function
0
-
No Change
Configured warning mask is not modified.
1
-
Activate everything
The warnings and controller status messages stated
are linked in the warning mask.
2
-
Activate all Warnings
The warnings reports stated are linked in the warn-
ing mask.
3
-
Activate all Controller
States
The controller status reports stated are linked in the
warning mask.
10
-
Warning Ixt
The frequency inverter is overloaded.
11
-
Warning Short-Term Ixt
Overload reserve for 1 s less the
Warning limit
short-term Ixt
405
has been reached.
12
-
Warning Long-Term Ixt
Overload reserve for 60 s less the
Warning limit
long-term Ixt
406
has been reached.
13
-
Warning Heat Sink
Temperature
Max. heat sink temperature T
K
of 80 °C minus the
Warning Limit
Heat Sink Temp.
407
has been
reached.
14
-
Warning Inside Tem-
perature
Max. inside temperature T
i
of 65 °C minus the
Warning Limit Inside Temp.
408
reached.
15
-
Warning Limit
The controller stated in
Controller status
355
limits
the reference value.
16
-
Warning Init
Frequency inverter is being initialized.
17
-
Warning Motor Tem-
perature
Warning behavior according to parameterized
Op-
eration mode Motor temperature
570
at max. motor
temperature T
PTC
.
18
-
Warning
Mains Failure
Phase monitoring
576
reports a phase failure.
19
-
Warning Motor Protec-
tive Switch
Operation Mode
571
for the motor protective
switch has triggered.
20
-
Warning Fmax
The
Maximum frequency
419
has been exceeded.
The frequency limitation is active.
21
-
Warning
Analog Input MFI1A
The input signal is lower than 1V/2mA according to
the operation mode
Error/Warning Behavior
453
.
22 -
Warning
Analog Input EM-S1INA
The input signal on the analog input of an expansion
module is lower than 1V/2mA according to the op-
eration mode
Error/Warning Behavior
453
.
23 -
Warning
System bus
A slave on the system bus reports a fault;
warning is only relevant with the EM-SYS option.
24 -
Warning Udc
The DC link voltage has reached the type-dependent
minimum value.
25 -
Application Warning
A warning application is signaled.
30 -
Controller
Udc Dynamic Operation
Controller is active according to the
Operation Mode
670
for the voltage controller.
31 -
Controller Shutdown
The output frequency in the case of a power failure
is below the
Shutdown threshold
675
.
32 -
Controller Mains Failure
Failure of the mains voltage and power regulation
active according to
Operation Mode
670
for the
voltage controller.
33 -
Controller Udc Limita-
tion
The DC link voltage has exceeded the
Reference UD
limitation
680
.
34 -
Controller
Voltage Pre-Control
The
Dyn. Voltage Pre-Control
605
accelerates the
control characteristics.