16.3 Technology
Controller
The technology controller, the behavior of which corresponds to a PID controller, is
available as an additional function in configuration 111, 211 and 411. The connection
of reference and actual value of the application with the functions of the frequency
inverter enables process control without further components. In this way, applications
such as pressure, volume flow or speed control can be implemented easily. The con-
figuration of the reference percentage source and the assignment of the actual per-
centage source are to be considered.
Structural image: Technology Controller
-
Technology controller
Reference
percentage source
476
Actual percentage source
478
Actual values:
Actual percentage value
230
Reference percentage value
229
Comply with the following chapters of the manual:
Parameter Chapter
Controller reference value:
Reference Percentage Source
476
13.5 „Reference percentage channel“
Monitoring of the current controller
reference value:
Reference Percentage Value
229
18.1 „Actual Values of the Frequency In-
verter“
Controller actual value:
Actual Percentage Source
478
is:
16.3 „Technology Controller“
- Analog signal at multifunction input:
Operation
Mode
452
14.1 „Multi-Function Input MFI1“
- Frequency signal at a digital input:
Operation
Mode
496
13.11 „PWM-/repetition frequency input“
Monitoring of the current controller
actual value:
Actual Percentage Value
230
18.1 „Actual Values of the Frequency In-
verter“
For the reference value, the technology controller also demands the assignment of an
analog application figure with the parameter
Actual percentage source
478
. The dif-
ference between reference and actual value is used by the technology controller to
control the drive system. The measured actual value is mapped via a signal converter
onto the input signal of the reference percentage source.
Actual percentage source
478
Function
1 -
Analog input MFI1A
The analog signal on the multifunction input 1 in
Operation mode
452
- analog operation.
32 -
Repetition frequency
input (F3)
The frequency signal on the digital input corre-
sponding to the selected
Operation mode
496
.