KFU 2-/4-
100
8.8 Language
The parameters are stored in the frequency inverter in various languages. The pa-
rameter description is displayed by the PC control software (e.g. VPlus) in the se-
lected
Language
33
.
Language
33
Function
0 - Deutsch
Parameter description in German.
1 - English
Parameter description in English.
2 - Italiano
Parameter description in Italian.
8.9 Programming
The parameter
Program(ming)
34
enables acknowledgment of a fault message and
resetting to the factory settings. The display of the control unit reads "dEFLt" or "rE-
SEt" and the LEDs indicate the status of the frequency inverter.
Program(ming)
34
Function
111
-
Parameter trans-
mission
Control unit P 500 is prepared for parameter transmis-
sion. A connected frequency inverter can receive data
from the control unit.
110
-
Standard opera-
tion
Resetting of control unit KP 500 to standard operation
mode
123 -
Reset
The current error message can be acknowledged via
digital input S1IND/STOA or the software parameter.
The display of the control unit reads "rESEt".
4444 -
Default
The parameters of the selected configuration, except for
a few exceptions, are reset to the default settings. The
display of the control unit reads "dEFLt".
Note:
Parameters
Control level
28
,
Language
33
as well as
Configuration
30
are not changed during resetting to factory settings (
Program(ming)
34
= 4444).