KFU 2-/4-
156
14.2.1.1 Output
Characteristic
The voltage range of the output signal at multifunction output 1 can be adjusted. The
value range of the actual value selected via parameter
Analog operation
553
is as-
signed to the value range of the output signal which is adjusted via the parameters
Voltage 100%
551
and
Voltage 0%
552
.
Parameter
Settings
No.
Description
Min.
Max.
Fact. sett.
551 Voltage 100%
0.0 V
22.0 V
10.0 V
552 Voltage 0%
0.0 V
22.0 V
0.0 V
Analog Operation
553
with abs. act.
value:
Analog operation
553
with signs:
0V
+10V
+24V
50%
0%
100%
0V
+5V
+24V
0%
-100%
100%
+10V
With the parameters
Voltage 100%
551
and
Voltage 0%
552
, the voltage range at
100% and 0% of the output parameter is set. If the output value exceeds the refer-
ence value, the output voltage also exceeds the value of the parameter
Voltage
100%
551
up to the maximum value of 24V.
14.2.2 Frequency Output MFO1F
The multifunctional output MFO1 can be used as a frequency output in the setting of
Operation Mode
550 =
“3 - Repetition Frequency”. The DC 24V output signal is as-
signed to the abs. value of the speed or frequency via the parameter
Repetition Freq.
Operation
555
. The selection of the operation modes depends on the extension
modules installed as an option.
Repetition Freq. Operation
555
Function
0
-
Off
Repetition frequency operation MFO1 switched
off
1 - Actual Frequency
Abs. value of the
Actual frequency
241
.
2 - Stator Frequency
Abs. value of the
Stator frequency
210
.
3 - Frequency Speed Sensor 1 Abs. value of the
Encoder 1 Frequency
217
.
5 - Repetition Frequency Input Abs. value of the
Repetition freq. input
252
.
14.2.2.1 Scaling
The repetition frequency mode for the multifunction output corresponds to the map-
ping of an incremental sensor. The parameter
Division marks
556
must be param-
eterized according to the frequency to be output.
Parameter
Settings
No.
Description
Min.
Max.
Fact. sett.
556
Division
Marks
30
8192
1024
The frequency limit of f
max
=150 kHz may not be exceeded in the calculation of the pa-
rameter
Division marks
556
.