Installation and operating manual
KT-Elektronik
CO4: Domestic water circuit
F
Function
FS
Function block parameter description/value range (factory default
setting)
14
Thermal
disinfection
0
CO4 -> F14 - 1 only with CO4 -> F01 - 1
Function block parameters:
Day of week / 1, 2, …, 7, 1–7 (3)
Start time / 00:00 to 23:45 (00:00),
Stop time / 00:00 to 23:45 (04:00)
Disinfection temperature / 60 to 90 °C (70 °C)
Boost of set-point / 0 to 50 °C (10 °C)
with start time = stop time Choice: bE / 1, 0 (1)
F Function block number, FS Factory default setting
CO5: system wide functions (all system variants)
If the controller signalizes CO5 -> F00 - 1, any access to return flow, volume flow rate and power
settings is locked.
F
Function
F
S
Function block parameter description/value range
(factory default setting)
01
02
03
Sensor initialization
1
Pt 1000
04 Summer operating mode
(OM)
0
CO5 -> F04 - 1: Activation of time-dependent summer
operating mode;
Function block parameters:
Beginning of summer period /01.01 to 31.12 (01.06)
Number of days needed for activation / 1 to 3 (2)
End of summer period / 01.01 to 31.12 (30.09)
Number of days needed for deactivation / 1 to 3 (1)
Outside temperature threshold /0 to 30 °C (18 °C)
05
Delayed outside temperature
compensation at dropping
temperatures
0
06
Delayed outside temperature
compensation at increasing
temperatures
0
CO5 -> F05, 06 - 1: Function block parameter:
Delay / 1 to 6 °C/h (3 °C/h)
08 Summertime-/ Wintertime-
switching
1
72
EB_37383_SOL3-3_EN002
Summary of Contents for SOL3-3
Page 1: ...Solar controller SOL3 3 Installation and operating manual Firmware version 1 07 April 2011...
Page 66: ...Installation and operating manual KT Elektronik Figure 12 Mounting 66 EB_37383_SOL3 3_EN002...
Page 86: ...Installation and operating manual KT Elektronik 86 EB_37383_SOL3 3_EN002...
Page 87: ...KT Elektronik SOL3 3 EB_37383_SOL3 3_EN002 87...