Installation and operating manual
KT-Elektronik
Storage tank priority
Depending on the usage, it could make sense to reach a higher temperature in one of
both storage tanks or to reach a uniform allocation of the collected energy. The
parameter Type of storage tank priority is used to determine the solar controller mode of
operation.
Setting
FS
Value range
Description
Type of storage tank
priority
3
1...5
The following table
Priority
mode
Function
Description
1
hard priority
Max
Storage tank 2 is only charged if the maximum temperature in
storage tank 1 has been reached
2
hard priority
Min.
Storage tank 2 is only charged if the minimum temperature in
storage tank 1 has been exceeded.
(defined at auxiliary heating, see section 5.14)
3
soft priority Storage tank 1 is always charged if the collector temperature is
sufficient to charge it. If not sufficient to charge storage tank 1
but sufficient to charge storage tank 2, charging of storage tank
2 is initiated. After the lapse of the specified time (Charging
time for low priority storage tank, WE15 minutes), charging is
interrupted for the minimum idle time (see section 5.1). At the
end of this interruption it is newly decided if the temperature is
sufficient to charge storage tank 1.
4
alternating
charge
The storage with the lowest temperature is charged first. Once
the currently charged storage tank becomes warmer by more
than 5K compared to the other one, charging is switched to the
colder storage tank. Switching can occur several times.
5
no priority
Both storages tank are charged having equal priority, that is,
the storage tank with the lower temperature is charged first. If
charging is not interrupted, the storage tank is charged to its
maximum temperature and only then switched to charge the
other storage tank.
5.3 Swimming pool
The solar controller SOL3 is suitable for the solar heating of swimming-pools. Any usable
solar energy is transferred in a swimming pool, which can be selected as a storage tank
1 or storage tank 2 with the given storage tank priority mode.
The maximum storage tank temperature (temperature of the swimming-pool) is to the
need to adapt.
38
EB_37383_SOL3-3_EN002
Summary of Contents for SOL3-3
Page 1: ...Solar controller SOL3 3 Installation and operating manual Firmware version 1 07 April 2011...
Page 66: ...Installation and operating manual KT Elektronik Figure 12 Mounting 66 EB_37383_SOL3 3_EN002...
Page 86: ...Installation and operating manual KT Elektronik 86 EB_37383_SOL3 3_EN002...
Page 87: ...KT Elektronik SOL3 3 EB_37383_SOL3 3_EN002 87...