Installation and operating manual
KT-Elektronik
8.3 Temperature monitoring
If the temperature in one of the control circuits deviates more than 50 K from normal for
a period of 30 minutes, the error message "Err 6" is generated (temperature monitoring
alarm).
Functions
FS
Configuration
Temperature monitoring
0
CO5 -> F19 - 1
8.4 Error status register
The error status register is used to report controller or system failures. In modem
operating mode with error reporting function, each change of error status triggers a dial
up connection to the building control system (BCS) to report the status change. The
errors that should affect the error status register can be set after having entered the
access code 0025.
The default factory setting „465“ causes that only the error messages in bold in the
following table affect the error status register.
Error message Description
Decimal value
FS
Exampl
e
Err 1
Sensor failure
1
1
1
Err 2
-
2
Err 3
-
4
Err 4
Max. charging temperature reached 8
Err 5
16
16
Err 6
Temperature monitoring alarm
32
32
Err 7
Unauthorized access
64
64
Err 8
-
128
128
Err 9
-
256
256
Sum
Sum
Factory default setting, access code 0025 =
465
Example: Error status register if sensor failure and alarm =
33
54
EB_37383_SOL3-3_EN002
Summary of Contents for SOL3-3
Page 1: ...Solar controller SOL3 3 Installation and operating manual Firmware version 1 07 April 2011...
Page 66: ...Installation and operating manual KT Elektronik Figure 12 Mounting 66 EB_37383_SOL3 3_EN002...
Page 86: ...Installation and operating manual KT Elektronik 86 EB_37383_SOL3 3_EN002...
Page 87: ...KT Elektronik SOL3 3 EB_37383_SOL3 3_EN002 87...