Installation and operating manual
KT-Elektronik
A dialling pause (approx 3 to 5 minutes) should be kept within two BCS/SMS provider
calls in order not to permanently stress the telecommunication network. The modem
dialling pause is programmed as period between two dial attempts.
Modem time out (T)
If connected to the BCS, but not addressing a Modbus data point, the controller closes
the connection after the modem has timed out. If the error status register has not been
read out during the connection to the BCS, the controller attempts to reconnect to the
BCS after the programmed modem dialling pause (P) to repeat the procedure. The time
setting is irrelevant for SMS delivery.
Number of dial attempts (C)
The dial attempts are repeated in compliance with the modem dialling pause as long as
the BCS/SMS service centre line is occupied respectively the call initiation has not been
reset by the building control system. Unsuccessful connection attempts are indicated by
"OFF" at the advanced information level. The dialling attempts counter is automatically
reset at 12:00 followed by new attempts.
Resetting the call initiation = reading out the error status register (HR40150)
Phone number of the BCS (TELnr)
The phone number of the building control system, including area code – if needed – has
to be entered here. Short dialling breaks can be provided by entering a "P", where each
P equals 1 second, the end of the dialling string has to be indicated by entering „–“. The
phone number can be up to 22 characters long.
Example phone number „069, 2 seconds break, 4009, 1 second break, 0“:
0 6 9 P P 4 0 0 9 P 0 – (= 11 characters)
9.7 Memory module
The memory module ParaMem (Mat-No. 17090) is especially suitable to transfer all
programmed data from one SOL3 controller to several other SOL3 controller. The
connector for the memory module is located on the left side (front panel view) inside the
controller housing (RJ45 connector). If successfully plugged in, “S3 SP” will be displayed
on the screen of the controller. If the memory module already contains data from another
SOL3 controller, they can be accessed by turning the rotary pushbutton to "SP S3".
By pressing the rotary pushbutton in "S3 SP" position, the current controller
settings are copied to the module.
By pressing the rotary pushbutton in "SP S3" position, the current module data is
copied to the controller and the display of "LESE".
The displayed bar graph is used as progress bar during the transfer. "I.O." is displayed to
confirm the completion of a successful data transfer. The memory module can now be
disconnected by unplugging it.
62
EB_37383_SOL3-3_EN002
Note:
By activating the function block CO6 -> F04 - 1, the connected modem is
configured automatically.
Summary of Contents for SOL3-3
Page 1: ...Solar controller SOL3 3 Installation and operating manual Firmware version 1 07 April 2011...
Page 66: ...Installation and operating manual KT Elektronik Figure 12 Mounting 66 EB_37383_SOL3 3_EN002...
Page 86: ...Installation and operating manual KT Elektronik 86 EB_37383_SOL3 3_EN002...
Page 87: ...KT Elektronik SOL3 3 EB_37383_SOL3 3_EN002 87...