Installation and operating manual
KT-Elektronik
11.3.1 Connecting the sensors
Wires with a minimum diameter of 2 by 0.5 mm² may be connected to the terminal strips
on the mounting panel.
Connecting the actuators
3-point-/2-point duty outputs: moisture proof cables with a minimum diameter of 1.5 mm²
are to be connected to the terminals of the controller output. It is recommended to check
the direction of rotation at start-up time.
Note: The motor actuators are not automatically supplied with power from the
controller. They can be connected to an external power source via terminal 28. If this is
not desired, jumper have to be set from terminal 18 to 28.
11.3.2 Connecting the pumps
All wires with a minimum diameter of 1.5 mm² are to be connected to the controller
according the wiring diagram. The relay outputs are isolated/potential-free contactors,
thus not supplied with power from the controller. Therefore, the terminals 20, 22 and 25
– and eventually 28 have to be connected to L1 (terminal 18).
11.3.3 Legend for connection diagram
CRF
Collector return-flow sensor
CP
Collector pump
CVF
Collector flow sensor
SP
Storage (charging) pump
SF
Storage sensor
CUV
Collector switching valve
CF
Collector sensor
SUV
Storage switching valve
VST-Imp. Volume flow impulses
RUV
Return flow switching valve
CTP
Collector exchanger pump
NH
Auxiliary heating
ZP
Domestic water-
circulation pump
flow
0..10V output for
pump rotation speed
68
EB_37383_SOL3-3_EN002
Summary of Contents for SOL3-3
Page 1: ...Solar controller SOL3 3 Installation and operating manual Firmware version 1 07 April 2011...
Page 66: ...Installation and operating manual KT Elektronik Figure 12 Mounting 66 EB_37383_SOL3 3_EN002...
Page 86: ...Installation and operating manual KT Elektronik 86 EB_37383_SOL3 3_EN002...
Page 87: ...KT Elektronik SOL3 3 EB_37383_SOL3 3_EN002 87...