KT-Elektronik
SOL3-3
7.3 Locking manual operating mode
This function can be used to lock the manual operating mode in order to protect the
heating system. When activated, the system is run in automatic mode when the rotary
switch is positioned at
.
Functions
FS
Configuration
Locking manual operating mode
0
CO5 -> F21 - 1
7.4 Locking the rotary switch
When activated, the system is run in automatic mode regardless of the rotary switch
position. No further settings can be programmed using the rotary switch.
Functions
FS
Configuration
Locking the rotary switches
0
CO5 -> F22 - 1
7.5 Enter a valid individual access code
The standard access code can be replaced by an individual code to prevent
unauthorized function or parameter changes. The individual code can be selected from
0100 to 1900.
Procedure:
Switch to configuration and settings level.
Display shows 0 0 0 0
Enter access code 1995.
Confirm code.
Enter a valid access code.
Confirm code.
Code flashes.
Enter individual code.
Confirm entered code.
The new valid code is from now on the one confirmed.
Move the rotary switch back to the "Information level" position
(left hand).
EB_37383_SOL3-3_EN002
51