1.8.5.3
DC surge protection, 2 poles
To avoid any lightning introduction inside the shelter Kerlink recommends using the
following bipolar DC surge protection: DS72R-48DC from CITEL.
A picture of DS72R-48DC is presented in Figure 70.
The following schematic shows electrical connections of the biipolar DC surge protection to
the Wirnet iBTS and the isolated DC/DC converter:
Figure 75 : DC surge protection 2 poles schematic
Kerlink recommends realizing a good direct connection between the Bipolar DC surge
protection and the earthing system of the installation. The used earthing cable must be as
short as possible (< 50 cm, 4 sq. mm).
The principles of cablig remain identical to those described in §1.8.5.2.
48V
Wirnet iBTS
DC/DC
Isolated
48V
Unipolar
DC surge protection