62
Error messages and diagnostics
ServoOne User Manual SERCOS II and III
ID no.: 1108.26B.3-00 Date: 04/2020
Error messages and diagnostics
10.1.2 Warning messages in the state class 2 (C2D)
Warning messages are displayed with the aid of the standard parameter S-0-0012
(state class 2).
The drive signals the warning by setting bit 12 in the drive status word (see chapter
5.2.4).
The following warnings are defined in the state class 2:
Bit no.
Warning
15
Manufacturer-specific warning
14
Reserved
13
Target position outside the positioning range
12
Communication warning
11
Excessive speed error
10
Reserved
9
Warning undervoltage bus
8 – 6
Reserved
5
Positioning speed > nLimit
4
Reserved
3
Warning cooling error
2
Warning overtemperature motor
1
Warning overtemperature amplifier
0
Warning overload
Table 10.2
State class 2
Bit = 0 warning not active, bit = 1 warning active.
10.1.3 Status messages (only SERCOS II)
The most important status messages from the drive are displayed in parameter S-0-
0013
(state class 3). The status messages in square brackets are defined in the SERCOS
specification, but are not supported by the ServoOne.
Parameter
Description
S-0-0013
Class 3 diagnostic (C3D)
Messages in the operating states
If the state of a drive changes, then the related bit in C3D is changed accordingly and
the change bit for C3D (bit 11) in the drive status is set to "1". The change bit for C3D
in the drive status is cleared to "0" again by reading C3D via the service channel. The
action of the operating state messages on the change bit in the drive status can be
eliminated in the mask for C3D (S-0-0098).
The bits defined in C3D are also defined by the parameter numbers given in brackets.
Structure of parameter C3D:
Bit 0: nactual = nref (see S-0-0330)
Bit 1: nactual = 0 (see S-0-0331)
Bit 2: |nactual| < |nx| (see S-0-0332)
Bit 3: |T| > | |Tx| (see S-0-0333)
[Bit 4: |T| > | |Tlimit| (see S-0-0334)]
Bit 5: |nref| > |n limit| (see S-0-0335)
Bit 6: Target position reached (see S-0-0336)
[Bit 7: |P | > |Px| (see S-0-0337)]
[Bit 8: Position actual value = Active target position
|(S-0-0430 – S-0-0051/0053)| < S-0-0057 (see S-0-0338)]
[Bit 9: |nfeedback| < Minimum spindle speed (see S-0-0339)]
[Bit 10: |nfeedback| > Maximum spindle speed (see S-0-0340)]
[Bit 11: Pre-position reached (see S-0-0341, S-0-0261)]
[Bit 12: Position reference value = Target position (see S-0-0342)]
[Bit 13: Positioning process interrupted (see S-0-0343)]
[Bit 14: Reserved]
[Bit 15: Manufacturer-specific status message set (see S-0-0182)]
Bit = 0 Status not active
Bit = 1 Status active
Table 10.3
Structure of parameter S-0-0013 (state class 3)
Summary of Contents for ServoOne Series
Page 10: ...10 ServoOne User Manual SERCOS II and III ID no 1108 26B 3 00 Date 04 2020...
Page 54: ...54 ServoOne User Manual SERCOS II and III ID no 1108 26B 3 00 Date 04 2020...
Page 78: ...78 ServoOne User Manual SERCOS II and III ID no 1108 26B 3 00 Date 04 2020...
Page 84: ...84 ServoOne User Manual SERCOS II and III ID no 1108 26B 3 00 Date 04 2020...
Page 85: ...85 ServoOne User Manual SERCOS II and III ID no 1108 26B 3 00 Date 04 2020...