V6R VRF 50Hz
Part 2 - Out
door Unit Engineering Da
ta
Mini Amazon III Series
13
Notes:
1. The cooling conditions: indoor temp: 27°CDB (80.6°F), 19°CWB (66.2°F) outdoor temp: 35°CDB (95°F) equivalent pipe length: 5m drop
length: 0m.
2. The heating conditions: indoor temp: 20°CDB (68°F), 15°CWB (44.6°F) outdoor temp.: 7°CDB (42.8°F) equivalent pipe length: 5m drop
length: 0m.
3. Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of *m(1m for 80/105 model,1.2m
for 120~160 model). During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. The above data may be changed without notice for future improvement on quality and performance.
Table 2-1.2: 140/160 model specifications
Sale Model
KMF-140 DVN4
KMF-160 DVN4
Power supply
V-Ph-Hz
220-240V~50Hz
220-240V~50Hz
Cooling
Capacity
kW
14
15.5
Input
kW
4.56
5.35
EER
kW/ KW
3.07
2.90
Heating
Capacity
kW
16
18
Input
kW
4.08
5.71
COP
kW/ kW
3.92
3.20
Compressor
Model
ATF400D64UMV
ATF400D64UMV
Type
Rotary
Rotary
Brand
GMCC
GMCC
Capacity
Btu/h
41957
41957
Input
W
3365
3365
Rated current(RLA)
A
6.5
6.5
Crankcase
W
25
25
Refrigerant oil
ml
RB74AF
RB74AF
400ml
500ml
Outdoor
fan motor
Model
WZDK170-38G-1
WZDK170-38G-1
Type
DC motor
DC motor
Brand
Welling/Panasonic/NIDEC
Welling/Panasonic/NIDEC
Insulation class
E
E
Safe class
IPX4
IPX4
Input
W
195
195
Output
W
170
170
Rated current
A
1.52
1.52
Speed
r/min
800
800
Outdoor air flow
m
3
/h
5400
5200
Outdoor sound
level
sound pressure level
dB(A)
56
56
Sound power level
dB(A)
71
71
Outdoor Unit
Dimension(W x H x D)
mm
1040 x 865 x 523
1040 x 865 x 523
Packing (W x H x D)
mm
1120 x 980 x 560
1120 x 980 x 560
Net/Gross weight
kg
91.4/101.4
95.4/105.4
Refrigerant
Type
R410A
R410A
Charged volume
g
3400
3800
Throttle type
Electronic expansion valve
Design pressure
MPa
4.4/2.6
Refrigerant piping
Liquid side/ Gas side
mm
Ф9.53/Ф15.9
Ф9.53/Ф19.1
Summary of Contents for KMF-100 DVN4