Mini Amazon III Series
84
Table 2-7.9: KMF-140 DVN4 heating capacity (continued)
Combination (%) (Capacity
index)
Outdoor temperature
(°C DB)
Indoor temperature(°C WB)
16.00
18.00
20.00
21.00
22.00
24.00
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
°C DB
°C WB
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
90%
-13.7
-15
13.46
4.94
13.41
5.00
13.41
5.05
13.36
5.07
13.31
4.87
12.19
4.38
-11.8
-13
13.66
4.96
13.61
5.00
13.61
5.06
13.56
5.01
13.31
4.77
12.19
4.30
-9.8
-11
13.87
4.96
13.87
5.01
13.82
5.06
13.82
4.91
13.31
4.68
12.19
4.22
-9.5
-10
13.97
4.97
13.97
5.01
13.92
5.07
13.87
4.86
13.31
4.63
12.19
4.17
-8.5
-9.1
14.07
4.97
14.02
5.02
14.02
5.06
13.87
4.82
13.31
4.59
12.19
4.14
-7
-7.6
14.22
4.98
14.22
4.95
14.17
4.98
13.87
4.75
13.31
4.52
12.19
4.08
-5
-5.6
15.34
4.99
15.29
4.74
14.43
4.78
13.87
4.59
13.31
4.38
12.19
3.96
-3
-3.7
15.54
4.99
15.49
4.53
14.43
4.54
13.87
4.42
13.31
4.24
12.19
3.86
0
-0.7
15.85
5.00
15.49
4.30
14.43
4.35
13.87
4.21
13.31
4.03
12.19
3.76
3
2.2
16.61
5.01
15.49
4.08
14.43
4.10
13.87
4.05
13.31
3.85
12.19
3.63
5
4.1
16.61
4.88
15.49
3.87
14.43
3.91
13.87
3.84
13.31
3.67
12.19
3.49
7
6
16.61
4.25
15.49
3.80
14.43
3.66
13.87
3.52
13.31
3.38
12.19
3.10
9
7.9
16.61
3.99
15.49
3.73
14.43
3.48
13.87
3.35
13.31
3.23
12.19
2.99
11
9.8
16.61
3.75
15.49
3.53
14.43
3.31
13.87
3.20
13.31
3.09
12.19
2.88
13
11.8
16.61
3.55
15.49
3.35
14.43
3.16
13.87
3.07
13.31
2.97
12.19
2.79
15
13.7
16.61
3.40
15.49
3.23
14.43
3.06
13.87
2.97
13.31
2.89
12.19
2.72
80%
-13.7
-15
13.41
4.97
13.36
5.02
12.80
4.59
12.29
4.38
11.83
4.17
10.82
3.77
-11.8
-13
13.61
4.97
13.56
4.92
12.80
4.50
12.29
4.29
11.83
4.09
10.82
3.70
-9.8
-11
13.82
4.98
13.77
4.82
12.80
4.41
12.29
4.21
11.83
4.02
10.82
3.63
-9.5
-10
13.92
4.99
13.77
4.78
12.80
4.37
12.29
4.17
11.83
3.98
10.82
3.60
-8.5
-9.1
14.02
4.99
13.77
4.74
12.80
4.33
12.29
4.13
11.83
3.94
10.82
3.57
-7
-7.6
14.17
5.00
13.77
4.67
12.80
4.27
12.29
4.08
11.83
3.89
10.82
3.52
-5
-5.6
14.78
4.90
13.77
4.51
12.80
4.14
12.29
3.95
11.83
3.78
10.82
3.42
-3
-3.7
14.78
5.07
13.77
4.35
12.80
3.96
12.29
3.80
11.83
3.64
10.82
3.32
0
-0.7
14.78
5.00
13.77
4.15
12.80
3.83
12.29
3.69
11.83
3.53
10.82
3.25
3
2.2
14.78
4.62
13.77
3.91
12.80
3.61
12.29
3.56
11.83
3.40
10.82
3.12
5
4.1
14.78
4.23
13.77
3.70
12.80
3.44
12.29
3.42
11.83
3.24
10.82
3.05
7
6
14.78
3.71
13.77
3.46
12.80
3.22
12.29
3.09
11.83
2.98
10.82
2.74
9
7.9
14.78
3.52
13.77
3.30
12.80
3.08
12.29
2.98
11.83
2.87
10.82
2.66
11
9.8
14.78
3.34
13.77
3.15
12.80
2.96
12.29
2.87
11.83
2.77
10.82
2.59
13
11.8
14.78
3.19
13.77
3.02
12.80
2.86
12.29
2.77
11.83
2.69
10.82
2.53
15
13.7
14.78
3.08
13.77
2.93
12.80
2.78
12.29
2.71
11.83
2.63
10.82
2.49
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (comp outdoor fan motor) (kW)
Notes:
1. Shaded cells are tested under our standard condition.
2. Avoid running the outdoor unit when outdoor air temperature is below -15 degrees in heating mode.
3. The above table shows the average value of conditions may operate.
4. It is recommended to connect less than 130%.