Mini Amazon III Series
88
Table 2-7.10: KMF-160 DVN4 heating capacity(continued)
Combination (%) (Capacity
index)
Outdoor temperature
(°C DB)
Indoor temperature(°C WB)
16.00
18.00
20.00
21.00
22.00
24.00
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
°C DB
°C WB
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
110%
-13.7
-15
15.26
5.72
15.20
5.85
15.14
5.98
15.14
5.83
15.14
5.94
15.09
6.09
-11.8
-13
15.49
5.81
15.43
5.93
15.43
6.06
15.37
5.89
15.37
6.01
15.31
6.16
-9.8
-11
15.71
5.81
15.66
5.94
15.66
6.06
15.60
6.00
15.60
6.08
15.54
6.24
-9.5
-10
15.83
5.87
15.83
6.00
15.77
6.13
15.71
6.02
15.71
6.16
15.66
6.30
-8.5
-9.1
15.94
5.94
15.89
6.06
15.89
6.19
15.83
6.07
15.83
6.22
15.77
6.37
-7
-7.6
16.11
6.00
16.06
6.13
16.06
6.25
16.00
6.16
16.00
6.29
15.94
6.39
-5
-5.6
17.37
6.08
17.31
6.21
17.26
6.33
17.26
6.22
17.26
6.33
16.74
6.32
-3
-3.7
17.60
6.13
17.54
6.25
17.49
6.38
17.49
6.28
17.49
6.41
16.74
6.21
0
-0.7
17.94
6.27
17.89
6.40
17.89
6.53
17.83
6.33
17.83
6.47
16.74
6.12
3
2.2
19.60
6.55
19.60
6.68
19.54
6.81
19.03
6.58
18.29
6.51
16.74
6.07
5
4.1
22.86
7.15
21.31
7.13
19.83
6.65
19.03
6.46
18.29
6.35
16.74
6.05
7
6
22.86
6.89
21.31
6.72
19.83
6.31
19.03
6.15
18.29
6.05
16.74
5.90
9
7.9
22.86
6.57
21.31
6.36
19.83
6.09
19.03
5.99
18.29
5.93
16.74
5.80
11
9.8
22.86
6.34
21.31
6.12
19.83
5.92
19.03
5.78
18.29
5.73
16.74
5.60
13
11.8
22.86
6.15
21.31
5.93
19.83
5.73
19.03
5.61
18.29
5.54
16.74
5.41
15
13.7
22.86
5.98
21.31
5.74
19.83
5.54
19.03
5.42
18.29
5.35
16.74
5.22
100%
-13.7
-15
15.43
6.83
15.37
6.89
15.37
6.98
15.31
7.01
15.31
7.05
15.26
6.88
-11.8
-13
15.66
6.84
15.60
6.91
15.60
6.98
15.54
7.03
15.54
7.06
15.26
6.80
-9.8
-11
15.77
6.84
15.77
6.92
15.71
6.99
15.71
7.03
15.66
7.07
15.26
6.79
-9.5
-10
15.89
6.85
15.83
6.92
15.83
7.01
15.77
7.03
15.77
7.08
15.26
6.73
-8.5
-9.1
16.06
6.86
16.06
6.93
16.00
7.03
15.94
7.04
15.94
7.08
15.26
6.63
-7
-7.6
17.31
6.87
17.26
6.93
17.26
7.18
17.20
7.30
16.63
6.94
15.26
6.61
-5
-5.6
17.54
6.88
17.49
6.93
17.49
7.01
17.31
7.09
16.63
6.74
15.26
6.42
-3
-3.7
17.89
6.89
17.83
6.94
17.83
6.78
17.31
6.68
16.63
6.52
15.26
6.21
0
-0.7
18.34
6.89
19.37
6.94
18.00
6.59
17.31
6.38
16.63
6.20
15.26
5.94
3
2.2
19.54
6.76
19.37
6.77
18.00
6.40
17.31
6.07
16.63
5.83
15.26
5.65
5
4.1
20.74
6.65
19.37
6.44
18.00
6.10
17.31
5.80
16.63
5.60
15.26
5.40
7
6
20.74
6.57
19.37
6.11
18.00
5.71
17.31
5.49
16.63
5.37
15.26
5.16
9
7.9
20.74
6.19
19.37
5.78
18.00
5.55
17.31
5.35
16.63
5.21
15.26
4.99
11
9.8
20.74
5.79
19.37
5.43
18.00
5.37
17.31
5.14
16.63
5.02
15.26
4.78
13
11.8
20.74
5.43
19.37
5.29
18.00
5.16
17.31
4.95
16.63
4.84
15.26
4.62
15
13.7
20.74
5.16
19.37
5.07
18.00
4.97
17.31
4.78
16.63
4.67
15.26
4.44
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (comp outdoor fan motor) (kW)
Notes:
1. Shaded cells are tested under our standard condition.
2. Avoid running the outdoor unit when outdoor air temperature is below -15 degrees in heating mode.
3. The above table shows the average value of conditions may operate.
4. It is recommended to connect less than 130%.