Mini Amazon III Series
86
Table 2-7.9: KMF-140 DVN4 heating capacity (continued)
Combination (%) (Capacity
index)
Outdoor temperature
(°C DB)
Indoor temperature(°C WB)
16.00
18.00
20.00
21.00
22.00
24.00
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
°C DB
°C WB
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
50%
-13.7
-15
9.24
3.46
8.63
3.28
8.03
3.15
7.67
3.02
7.37
2.93
6.76
2.70
-11.8
-13
9.24
3.34
8.63
3.16
8.03
3.03
7.67
2.92
7.37
2.81
6.76
2.58
-9.8
-11
9.24
3.23
8.63
3.04
8.03
2.89
7.67
2.79
7.37
2.69
6.76
2.49
-9.5
-10
9.24
3.12
8.63
2.92
8.03
2.77
7.67
2.67
7.37
2.57
6.76
2.35
-8.5
-9.1
9.24
2.99
8.63
2.82
8.03
2.65
7.67
2.55
7.37
2.46
6.76
2.22
-7
-7.6
9.24
2.87
8.63
2.70
8.03
2.56
7.67
2.47
7.37
2.36
6.76
2.12
-5
-5.6
9.24
2.77
8.63
2.60
8.03
2.43
7.67
2.36
7.37
2.27
6.76
2.02
-3
-3.7
9.24
2.67
8.63
2.49
8.03
2.32
7.67
2.27
7.37
2.17
6.76
1.95
0
-0.7
9.24
2.56
8.63
2.40
8.03
2.22
7.67
2.16
7.37
2.07
6.76
1.91
3
2.2
9.24
2.45
8.63
2.28
8.03
2.13
7.67
2.07
7.37
1.97
6.76
1.90
5
4.1
9.24
2.32
8.63
2.18
8.03
2.06
7.67
1.98
7.37
1.92
6.76
1.88
7
6
9.24
2.22
8.63
2.09
8.03
1.96
7.67
1.90
7.37
1.89
6.76
1.83
9
7.9
9.24
2.18
8.63
2.04
8.03
1.93
7.67
1.85
7.37
1.81
6.76
1.77
11
9.8
9.24
2.15
8.63
2.01
8.03
1.88
7.67
1.81
7.37
1.78
6.76
1.74
13
11.8
9.24
2.08
8.63
1.95
8.03
1.82
7.67
1.77
7.37
1.74
6.76
1.70
15
13.7
9.24
2.05
8.63
1.91
8.03
1.77
7.67
1.73
7.37
1.69
6.76
1.65
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (comp outdoor fan motor) (kW)
Notes:
1. Shaded cells are tested under our standard condition.
2. Avoid running the outdoor unit when outdoor air temperature is below -15 degrees in heating mode.
3. The above table shows the average value of conditions may operate.
4. It is recommended to connect less than 130%.