V6R VRF 50Hz
Part 2 - Out
door Unit Engineering Da
ta
Mini Amazon III Series
75
Table 2-7.7: KMF-100 DVN4 heating capacity (continued)
Combination (%) (Capacity
index)
Outdoor temperature
(°C DB)
Indoor temperature(°C WB)
16.00
18.00
20.00
21.00
22.00
24.00
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
°C DB
°C WB
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
70%
-13.7
-15
7.26
2.44
6.77
2.25
6.31
2.21
6.06
2.17
5.83
2.14
5.34
2.05
-11.8
-13
7.26
2.39
6.77
2.21
6.31
2.17
6.06
2.13
5.83
2.10
5.34
2.01
-9.8
-11
7.26
2.35
6.77
2.16
6.31
2.13
6.06
2.09
5.83
2.06
5.34
1.97
-9.5
-10
7.26
2.33
6.77
2.14
6.31
2.08
6.06
2.04
5.83
2.01
5.34
1.92
-8.5
-9.1
7.26
2.30
6.77
2.13
6.31
2.01
6.06
1.97
5.83
1.94
5.34
1.85
-7
-7.6
7.26
2.27
6.77
2.10
6.31
1.92
6.06
1.88
5.83
1.85
5.34
1.76
-5
-5.6
7.26
2.20
6.77
2.03
6.31
1.87
6.06
1.83
5.83
1.80
5.34
1.71
-3
-3.7
7.26
2.08
6.77
1.97
6.31
1.82
6.06
1.77
5.83
1.74
5.34
1.65
0
-0.7
7.26
1.97
6.77
1.89
6.31
1.74
6.06
1.69
5.83
1.66
5.34
1.58
3
2.2
7.26
1.86
6.77
1.78
6.31
1.63
6.06
1.59
5.83
1.56
5.34
1.47
5
4.1
7.26
1.78
6.77
1.67
6.31
1.57
6.06
1.53
5.83
1.50
5.34
1.41
7
6
7.26
1.71
6.77
1.60
6.31
1.49
6.06
1.45
5.83
1.42
5.34
1.33
9
7.9
7.26
1.63
6.77
1.54
6.31
1.44
6.06
1.40
5.83
1.37
5.34
1.28
11
9.8
7.26
1.57
6.77
1.48
6.31
1.38
6.06
1.34
5.83
1.31
5.34
1.22
13
11.8
7.26
1.51
6.77
1.42
6.31
1.32
6.06
1.27
5.83
1.24
5.34
1.15
15
13.7
7.26
1.46
6.77
1.36
6.31
1.27
6.06
1.22
5.83
1.19
5.34
1.10
60%
-13.7
-15
6.23
2.17
5.83
2.06
5.40
1.98
5.20
1.90
4.97
1.80
4.57
1.69
-11.8
-13
6.23
2.10
5.83
1.98
5.40
1.90
5.20
1.83
4.97
1.72
4.57
1.62
-9.8
-11
6.23
2.03
5.83
1.91
5.40
1.81
5.20
1.75
4.97
1.65
4.57
1.56
-9.5
-10
6.23
1.96
5.83
1.83
5.40
1.74
5.20
1.67
4.97
1.58
4.57
1.47
-8.5
-9.1
6.23
1.87
5.83
1.77
5.40
1.66
5.20
1.60
4.97
1.50
4.57
1.39
-7
-7.6
6.23
1.80
5.83
1.69
5.40
1.61
5.20
1.55
4.97
1.45
4.57
1.33
-5
-5.6
6.23
1.74
5.83
1.63
5.40
1.53
5.20
1.48
4.97
1.39
4.57
1.27
-3
-3.7
6.23
1.68
5.83
1.57
5.40
1.46
5.20
1.42
4.97
1.33
4.57
1.22
0
-0.7
6.23
1.61
5.83
1.50
5.40
1.39
5.20
1.36
4.97
1.26
4.57
1.20
3
2.2
6.23
1.54
5.83
1.43
5.40
1.34
5.20
1.30
4.97
1.20
4.57
1.16
5
4.1
6.23
1.46
5.83
1.37
5.40
1.29
5.20
1.24
4.97
1.17
4.57
1.13
7
6
6.23
1.39
5.83
1.31
5.40
1.23
5.20
1.19
4.97
1.16
4.57
1.11
9
7.9
6.23
1.37
5.83
1.28
5.40
1.21
5.20
1.16
4.97
1.11
4.57
1.06
11
9.8
6.23
1.35
5.83
1.26
5.40
1.18
5.20
1.14
4.97
1.09
4.57
1.04
13
11.8
6.23
1.30
5.83
1.22
5.40
1.14
5.20
1.11
4.97
1.07
4.57
1.02
15
13.7
6.23
1.29
5.83
1.20
5.40
1.11
5.20
1.08
4.97
1.04
4.57
0.99
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (comp outdoor fan motor) (kW)
Notes:
1. Shaded cells are tested under our standard condition.
2. Avoid running the outdoor unit when outdoor air temperature is below -15 degrees in heating mode.
3. The above table shows the average value of conditions may operate.
4. It is recommended to connect less than 130%.