V6R VRF 50Hz
Part 2 - Out
door Unit Engineering Da
ta
Mini Amazon III Series
85
Table 2-7.9: KMF-140 DVN4 heating capacity (continued)
Combination (%) (Capacity
index)
Outdoor temperature
(°C DB)
Indoor temperature(°C WB)
16.00
18.00
20.00
21.00
22.00
24.00
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
°C DB
°C WB
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
70%
-13.7
-15
12.90
4.70
12.04
4.33
11.23
4.25
10.77
4.17
10.36
4.11
9.50
3.94
-11.8
-13
12.90
4.61
12.04
4.25
11.23
4.18
10.77
4.10
10.36
4.04
9.50
3.87
-9.8
-11
12.90
4.52
12.04
4.16
11.23
4.11
10.77
4.02
10.36
3.96
9.50
3.79
-9.5
-10
12.90
4.48
12.04
4.13
11.23
4.00
10.77
3.92
10.36
3.86
9.50
3.69
-8.5
-9.1
12.90
4.43
12.04
4.09
11.23
3.87
10.77
3.78
10.36
3.73
9.50
3.55
-7
-7.6
12.90
4.38
12.04
4.03
11.23
3.70
10.77
3.62
10.36
3.56
9.50
3.39
-5
-5.6
12.90
4.24
12.04
3.91
11.23
3.60
10.77
3.52
10.36
3.46
9.50
3.29
-3
-3.7
12.90
4.01
12.04
3.80
11.23
3.50
10.77
3.41
10.36
3.35
9.50
3.18
0
-0.7
12.90
3.80
12.04
3.63
11.23
3.35
10.77
3.26
10.36
3.20
9.50
3.03
3
2.2
12.90
3.58
12.04
3.43
11.23
3.14
10.77
3.06
10.36
3.00
9.50
2.83
5
4.1
12.90
3.42
12.04
3.21
11.23
3.02
10.77
2.94
10.36
2.88
9.50
2.71
7
6
12.90
3.29
12.04
3.07
11.23
2.87
10.77
2.79
10.36
2.73
9.50
2.56
9
7.9
12.90
3.15
12.04
2.96
11.23
2.77
10.77
2.69
10.36
2.63
9.50
2.46
11
9.8
12.90
3.02
12.04
2.86
11.23
2.66
10.77
2.58
10.36
2.52
9.50
2.35
13
11.8
12.90
2.91
12.04
2.74
11.23
2.53
10.77
2.45
10.36
2.39
9.50
2.22
15
13.7
12.90
2.80
12.04
2.62
11.23
2.43
10.77
2.35
10.36
2.29
9.50
2.12
60%
-13.7
-15
11.07
4.18
10.36
3.97
9.60
3.81
9.24
3.65
8.84
3.46
8.13
3.26
-11.8
-13
11.07
4.03
10.36
3.82
9.60
3.66
9.24
3.53
8.84
3.32
8.13
3.12
-9.8
-11
11.07
3.90
10.36
3.68
9.60
3.49
9.24
3.37
8.84
3.18
8.13
3.00
-9.5
-10
11.07
3.76
10.36
3.53
9.60
3.34
9.24
3.22
8.84
3.04
8.13
2.84
-8.5
-9.1
11.07
3.61
10.36
3.40
9.60
3.20
9.24
3.08
8.84
2.90
8.13
2.68
-7
-7.6
11.07
3.47
10.36
3.26
9.60
3.09
9.24
2.98
8.84
2.78
8.13
2.56
-5
-5.6
11.07
3.34
10.36
3.14
9.60
2.94
9.24
2.86
8.84
2.67
8.13
2.44
-3
-3.7
11.07
3.23
10.36
3.01
9.60
2.81
9.24
2.74
8.84
2.55
8.13
2.35
0
-0.7
11.07
3.10
10.36
2.89
9.60
2.68
9.24
2.61
8.84
2.43
8.13
2.31
3
2.2
11.07
2.96
10.36
2.76
9.60
2.58
9.24
2.50
8.84
2.30
8.13
2.22
5
4.1
11.07
2.81
10.36
2.64
9.60
2.48
9.24
2.39
8.84
2.25
8.13
2.18
7
6
11.07
2.68
10.36
2.53
9.60
2.37
9.24
2.29
8.84
2.24
8.13
2.13
9
7.9
11.07
2.63
10.36
2.47
9.60
2.33
9.24
2.24
8.84
2.14
8.13
2.04
11
9.8
11.07
2.59
10.36
2.43
9.60
2.27
9.24
2.19
8.84
2.10
8.13
2.00
13
11.8
11.07
2.51
10.36
2.35
9.60
2.20
9.24
2.14
8.84
2.06
8.13
1.96
15
13.7
11.07
2.48
10.36
2.30
9.60
2.13
9.24
2.09
8.84
2.00
8.13
1.90
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (comp outdoor fan motor) (kW)
Notes:
1. Shaded cells are tested under our standard condition.
2. Avoid running the outdoor unit when outdoor air temperature is below -15 degrees in heating mode.
3. The above table shows the average value of conditions may operate.
4. It is recommended to connect less than 130%.