Mini Amazon III Series
74
Table 2-7.7: KMF-100 DVN4 heating capacity (continued)
Combination (%) (Capacity
index)
Outdoor temperature
(°C DB)
Indoor temperature(°C WB)
16.00
18.00
20.00
21.00
22.00
24.00
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
°C DB
°C WB
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
90%
-13.7
-15
7.57
2.57
7.54
2.60
7.54
2.62
7.51
2.64
7.49
2.53
6.86
2.28
-11.8
-13
7.69
2.57
7.66
2.60
7.66
2.63
7.63
2.60
7.49
2.48
6.86
2.23
-9.8
-11
7.80
2.58
7.80
2.61
7.77
2.63
7.77
2.55
7.49
2.43
6.86
2.19
-9.5
-10
7.86
2.58
7.86
2.61
7.83
2.63
7.80
2.53
7.49
2.41
6.86
2.17
-8.5
-9.1
7.91
2.58
7.89
2.61
7.89
2.63
7.80
2.50
7.49
2.38
6.86
2.15
-7
-7.6
8.00
2.59
8.00
2.57
7.97
2.59
7.80
2.47
7.49
2.35
6.86
2.12
-5
-5.6
8.63
2.59
8.60
2.46
8.11
2.48
7.80
2.39
7.49
2.28
6.86
2.06
-3
-3.7
8.74
2.60
8.71
2.35
8.11
2.36
7.80
2.30
7.49
2.20
6.86
2.01
0
-0.7
8.91
2.60
8.71
2.24
8.11
2.26
7.80
2.19
7.49
2.10
6.86
1.95
3
2.2
9.34
2.60
8.71
2.12
8.11
2.13
7.80
2.11
7.49
2.00
6.86
1.89
5
4.1
9.34
2.54
8.71
2.01
8.11
2.03
7.80
2.00
7.49
1.91
6.86
1.81
7
6
9.34
2.21
8.71
1.98
8.11
1.90
7.80
1.83
7.49
1.76
6.86
1.61
9
7.9
9.34
2.07
8.71
1.94
8.11
1.81
7.80
1.74
7.49
1.68
6.86
1.55
11
9.8
9.34
1.95
8.71
1.83
8.11
1.72
7.80
1.66
7.49
1.61
6.86
1.50
13
11.8
9.34
1.84
8.71
1.74
8.11
1.64
7.80
1.59
7.49
1.55
6.86
1.45
15
13.7
9.34
1.77
8.71
1.68
8.11
1.59
7.80
1.55
7.49
1.50
6.86
1.41
80%
-13.7
-15
7.54
2.58
7.51
2.61
7.20
2.38
6.91
2.28
6.66
2.17
6.09
1.96
-11.8
-13
7.66
2.58
7.63
2.56
7.20
2.34
6.91
2.23
6.66
2.13
6.09
1.92
-9.8
-11
7.77
2.59
7.74
2.51
7.20
2.29
6.91
2.19
6.66
2.09
6.09
1.89
-9.5
-10
7.83
2.59
7.74
2.48
7.20
2.27
6.91
2.17
6.66
2.07
6.09
1.87
-8.5
-9.1
7.89
2.59
7.74
2.46
7.20
2.25
6.91
2.15
6.66
2.05
6.09
1.85
-7
-7.6
7.97
2.60
7.74
2.42
7.20
2.22
6.91
2.12
6.66
2.02
6.09
1.83
-5
-5.6
8.31
2.55
7.74
2.35
7.20
2.15
6.91
2.05
6.66
1.96
6.09
1.78
-3
-3.7
8.31
2.63
7.74
2.26
7.20
2.06
6.91
1.98
6.66
1.89
6.09
1.73
0
-0.7
8.31
2.60
7.74
2.16
7.20
1.99
6.91
1.92
6.66
1.84
6.09
1.69
3
2.2
8.31
2.40
7.74
2.03
7.20
1.88
6.91
1.85
6.66
1.77
6.09
1.62
5
4.1
8.31
2.20
7.74
1.92
7.20
1.79
6.91
1.77
6.66
1.68
6.09
1.59
7
6
8.31
1.93
7.74
1.80
7.20
1.67
6.91
1.61
6.66
1.55
6.09
1.43
9
7.9
8.31
1.83
7.74
1.71
7.20
1.60
6.91
1.55
6.66
1.49
6.09
1.38
11
9.8
8.31
1.74
7.74
1.64
7.20
1.54
6.91
1.49
6.66
1.44
6.09
1.35
13
11.8
8.31
1.66
7.74
1.57
7.20
1.48
6.91
1.44
6.66
1.40
6.09
1.31
15
13.7
8.31
1.60
7.74
1.52
7.20
1.44
6.91
1.41
6.66
1.37
6.09
1.29
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (comp outdoor fan motor) (kW)
Notes:
1. Shaded cells are tested under our standard condition.
2. Avoid running the outdoor unit when outdoor air temperature is below -15 degrees in heating mode.
3. The above table shows the average value of conditions may operate.
4. It is recommended to connect less than 130%.