V6R VRF 50Hz
Part 2 - Out
door Unit Engineering Da
ta
Mini Amazon III Series
87
Table 2-7.10: KMF-160 DVN4 heating capacity
Combination (%) (Capacity
index)
Outdoor temperature
(°C DB)
Indoor temperature(°C WB)
16.00
18.00
20.00
21.00
22.00
24.00
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
°C DB
°C WB
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
130%
-13.7
-15
15.33
5.18
15.27
5.31
15.22
5.54
15.22
5.68
15.16
5.83
15.10
5.90
-11.8
-13
15.56
5.26
15.50
5.40
15.44
5.64
15.44
5.78
15.39
5.93
15.39
5.99
-9.8
-11
15.78
5.35
15.73
5.50
15.67
5.70
15.67
5.84
15.67
5.99
15.61
6.00
-9.5
-10
15.90
5.43
15.84
5.55
15.84
5.79
15.78
5.93
15.78
6.08
15.73
6.09
-8.5
-9.1
16.01
5.50
15.96
5.63
15.90
5.85
15.90
5.99
15.90
6.14
15.84
6.16
-7
-7.6
16.18
5.51
16.13
5.71
16.13
5.90
16.07
6.04
16.07
6.23
16.01
6.24
-5
-5.6
17.44
5.75
17.38
5.87
17.32
6.09
17.32
6.27
17.27
6.27
17.21
6.31
-3
-3.7
17.67
5.89
17.61
5.96
17.55
6.19
17.55
6.37
17.49
6.35
17.44
6.40
0
-0.7
18.01
6.06
17.95
6.02
17.89
6.27
17.89
6.44
17.84
6.44
17.84
6.45
3
2.2
19.89
6.40
19.66
6.41
19.60
6.59
19.55
6.71
19.55
6.78
19.49
6.84
5
4.1
24.73
7.74
23.74
7.65
23.36
7.62
22.45
7.37
21.54
7.29
19.77
6.97
7
6
25.13
7.80
24.20
7.44
23.36
7.24
22.45
7.06
21.54
6.99
19.77
6.73
9
7.9
25.13
7.42
24.20
7.09
23.36
7.02
22.45
6.93
21.54
6.81
19.77
6.58
11
9.8
25.13
7.06
24.20
6.80
23.36
6.78
22.45
6.69
21.54
6.61
19.77
6.33
13
11.8
25.13
6.72
24.20
6.59
23.36
6.59
22.45
6.58
21.54
6.47
19.77
6.21
15
13.7
25.13
6.51
24.20
6.45
23.36
6.41
22.45
6.32
21.54
6.28
19.77
5.98
120%
-13.7
-15
15.31
5.65
15.26
5.81
15.20
5.97
15.20
6.11
15.20
6.24
15.14
6.29
-11.8
-13
15.54
5.73
15.49
5.87
15.45
6.05
15.43
6.18
15.43
6.32
15.37
6.36
-9.8
-11
15.77
5.77
15.71
5.91
15.71
6.12
15.66
6.25
15.66
6.39
15.60
6.48
-9.5
-10
15.89
5.83
15.83
5.95
15.83
6.16
15.77
6.29
15.77
6.43
15.71
6.57
-8.5
-9.1
16.00
5.89
15.94
6.03
15.94
6.23
15.89
6.36
15.89
6.50
15.83
6.57
-7
-7.6
16.17
5.99
16.11
6.14
16.11
6.30
16.06
6.43
16.06
6.57
16.00
6.65
-5
-5.6
17.43
6.04
17.37
6.19
17.31
6.36
17.31
6.50
17.31
6.64
17.26
6.76
-3
-3.7
17.66
6.15
17.60
6.29
17.54
6.44
17.54
6.58
17.49
6.72
17.49
6.79
0
-0.7
18.00
6.23
17.94
6.37
17.89
6.50
17.89
6.64
17.89
6.77
17.83
6.84
3
2.2
19.66
6.60
19.66
6.78
19.60
6.83
19.54
6.97
19.54
7.10
18.29
6.77
5
4.1
24.74
7.40
23.26
7.33
21.60
7.21
20.74
7.06
19.94
6.98
18.29
6.57
7
6
24.91
7.35
23.26
7.02
21.60
6.84
20.74
6.72
19.94
6.68
18.29
6.41
9
7.9
24.91
7.03
23.26
6.71
21.60
6.63
20.74
6.50
19.94
6.49
18.29
6.21
11
9.8
24.91
6.80
23.26
6.56
21.60
6.41
20.74
6.31
19.94
6.25
18.29
5.98
13
11.8
24.91
6.64
23.26
6.40
21.60
6.23
20.74
6.21
19.94
6.14
18.29
5.86
15
13.7
24.91
6.49
23.26
6.21
21.60
6.05
20.74
5.98
19.94
5.93
18.29
5.65
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (comp outdoor fan motor) (kW)
Notes:
1. Shaded cells are tested under our standard condition.
2. Avoid running the outdoor unit when outdoor air temperature is below -15 degrees in heating mode.
3. The above table shows the average value of conditions may operate.
4. It is recommended to connect less than 130%.