Mini Amazon III Series
82
Table 2-7.9: KMF-140 DVN4 heating capacity
Combination (%) (Capacity
index)
Outdoor temperature
(°C DB)
Indoor temperature(°C WB)
16.00
18.00
20.00
21.00
22.00
24.00
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
°C DB
°C WB
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
130%
-13.7
-15
13.63
3.70
13.58
3.80
13.52
3.96
13.52
4.06
13.47
4.16
13.42
4.22
-11.8
-13
13.83
3.76
13.78
3.86
13.73
4.03
13.73
4.13
13.68
4.24
13.68
4.28
-9.8
-11
14.03
3.82
13.98
3.93
13.93
4.07
13.93
4.17
13.93
4.28
13.88
4.29
-9.5
-10
14.13
3.88
14.08
3.97
14.08
4.13
14.03
4.24
14.03
4.34
13.98
4.35
-8.5
-9.1
14.23
3.93
14.18
4.02
14.13
4.18
14.13
4.28
14.13
4.39
14.08
4.40
-7
-7.6
14.39
3.93
14.33
4.08
14.33
4.22
14.28
4.32
14.28
4.45
14.23
4.46
-5
-5.6
15.50
4.11
15.45
4.19
15.40
4.35
15.40
4.48
15.35
4.48
15.30
4.51
-3
-3.7
15.70
4.21
15.65
4.26
15.60
4.42
15.60
4.55
15.55
4.54
15.50
4.57
0
-0.7
16.01
4.33
15.96
4.30
15.91
4.48
15.91
4.60
15.85
4.60
15.85
4.61
3
2.2
17.68
4.58
17.48
4.58
17.42
4.71
17.37
4.80
17.37
4.85
17.32
4.89
5
4.1
21.98
5.53
21.10
5.46
20.77
5.44
19.96
5.27
19.15
5.21
17.58
4.98
7
6
22.34
5.57
21.51
5.32
20.77
5.18
19.96
5.04
19.15
4.99
17.58
4.81
9
7.9
22.34
5.30
21.51
5.06
20.77
5.02
19.96
4.95
19.15
4.87
17.58
4.70
11
9.8
22.34
5.04
21.51
4.86
20.77
4.85
19.96
4.78
19.15
4.72
17.58
4.52
13
11.8
22.34
4.80
21.51
4.71
20.77
4.71
19.96
4.70
19.15
4.62
17.58
4.44
15
13.7
22.34
4.65
21.51
4.61
20.77
4.58
19.96
4.52
19.15
4.49
17.58
4.28
120%
-13.7
-15
13.61
4.04
13.56
4.15
13.51
4.27
13.51
4.36
13.51
4.46
13.46
4.50
-11.8
-13
13.82
4.10
13.77
4.19
13.74
4.32
13.71
4.42
13.71
4.52
13.66
4.55
-9.8
-11
14.02
4.12
13.97
4.22
13.97
4.37
13.92
4.47
13.92
4.57
13.87
4.63
-9.5
-10
14.12
4.17
14.07
4.25
14.07
4.40
14.02
4.50
14.02
4.60
13.97
4.69
-8.5
-9.1
14.22
4.21
14.17
4.31
14.17
4.45
14.12
4.55
14.12
4.65
14.07
4.70
-7
-7.6
14.37
4.28
14.32
4.39
14.32
4.50
14.27
4.60
14.27
4.69
14.22
4.75
-5
-5.6
15.49
4.32
15.44
4.42
15.39
4.55
15.39
4.64
15.39
4.74
15.34
4.83
-3
-3.7
15.70
4.39
15.64
4.49
15.59
4.60
15.59
4.70
15.54
4.80
15.54
4.85
0
-0.7
16.00
4.45
15.95
4.56
15.90
4.64
15.90
4.74
15.90
4.84
15.85
4.89
3
2.2
17.47
4.72
17.47
4.84
17.42
4.88
17.37
4.98
17.37
5.08
16.25
4.84
5
4.1
21.99
5.29
20.67
5.23
19.20
5.15
18.44
5.05
17.73
4.99
16.25
4.69
7
6
22.15
5.25
20.67
5.01
19.20
4.89
18.44
4.80
17.73
4.77
16.25
4.58
9
7.9
22.15
5.02
20.67
4.79
19.20
4.74
18.44
4.64
17.73
4.64
16.25
4.44
11
9.8
22.15
4.86
20.67
4.69
19.20
4.58
18.44
4.51
17.73
4.47
16.25
4.27
13
11.8
22.15
4.74
20.67
4.57
19.20
4.45
18.44
4.44
17.73
4.39
16.25
4.19
15
13.7
22.15
4.64
20.67
4.44
19.20
4.33
18.44
4.27
17.73
4.24
16.25
4.03
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (comp outdoor fan motor) (kW)
Notes:
1. Sha
re tested under our standard condition.
2. Avoid running the outdoor unit when outdoor air temperature is below -15 degrees in heating mode.
3. The above table shows the average value of conditions may operate.
4. It is recommended to con
s than 130%.